ICS-KP14 Instruction Manual
01850-53-000
Page 9 of 18
Issue 3 19 January 2021
5.1 Connecting to Lasermet ICS Control Panels
The ICS-KP14 may be connected such that it either overrides the individual door to which it is
associated (local override), or to override all doors in the system (global override).
Connecting to ICS-6, overriding only the associated door
Three of the screw terminals of J8 inside the keypad: +24V, O/R and 0V are wired directly to the
corresponding terminals of J7 inside the ICS-6 using suitable copper low-voltage cable. The O/R
connection allows the ICS-6 to signal an override when the keypad is operated.
The jumper link J6 ‘OVERRIDE CONTROL’ is removed so that the ICS-6 only indicates that an override
is active but isn’t actually overridden itself.
The two override output contacts A and B on J6 in the keypad are wired across the two safety contacts
of the door switch. This is the contact which is closed when the door is closed. When the override is
activated the keypad override contacts will maintain the safety circuit when the door contacts open.
IMPORTANT!
Ensure the plug-in jumper link J6 ‘OVERRIDE CONTROL’ on the ICS-6 Main Circuit Board is removed
(set open) so that the keypad can activate the override indications in the ICS-6 without actually
overriding it. If this link is left closed all the other doors in the system will be overridden at the same
time.