ICS-6 Instruction Manual
01000-53-000
Page 8 of 42
Issue 11 19 January 2021
3
Summary of Evaluation of Compliance to EN ISO 13849-1:2015
Note that this summary relates to the ICS-6 controller only. To achieve a complete system
performance level ‘e’ the system must be wired as described in this manual using suitably rated door
sensors and measures taken to minimise the effects of common cause failures in the sensors and
wiring which may be connected to the unit.
Required Characteristics:
Architecture
Category 3/4
Performance Level Required (PLr)
PLr = e
Application Demand Base:
In service operation
365 days/year
Functional demand on the controller once per hour
Achieved Characteristics:
Architecture
Category 4
Performance Level (PL)
PL = e
PFH [1/h]
2.47xE-8
MTTFd
100 years
Mission Time
20 years