background image

Laser Jailer Maintenance Manual 

 

00892-53-000 

Page 14 of 16

 

Issue 2          30 January 2020 

 
 

Open Circuit 

 
Lasermet  supply  a  probe  for  locating  open  circuits.  It  comprises  a  signal  source  and  a  handheld 
‘wand’.  The  signal  source  is  connected to  the  cable. The  wand  is  offered  close  to  each  tile  in  turn 
following the order in which they are interconnected. A meter indicates whether or not the signal is 
present and in this way the point of open circuit can be located. 
 
The wand can also be useful for confirming that none of the tiles have been bypassed or missed out. 
 
The unit is supplied with operating instructions. 
 
If the probe is not available, the circuit can be checked with the multimeter. One way is to remove a 
tile near the middle of the circuit and fit wires into the sockets of the remaining adjacent tiles such 
that the two pins are connected together. The meter, on resistance range, is then put across A Start 
and B Start. If the half circuit as far as the removed tile is OK a reading of less than 200kΩ should be 
seen. This is  repeated  for the  other  half circuit by measuring the  resistance  between  A End and  B 
End. Once the faulty half-circuit is found the tile is reconnected and replaced and a tile is removed 
near the middle of that half-circuit and the test repeated. In this way it is possible to progressively 
divide the circuit into smaller chunks until the fault is located. 
 

 
Leakage 

 
This technique can be used for faults between the two circuits, or between one circuit and earth. 
 
If the failed resistance test indicates a low value (e.g. less than about 5kΩ) and the reading is steady 
there could be an actual short circuit and its position can be predicted based on the theory that each 
tile adds 66 ohms to the resistance. For example, if the reading was 594Ω from the start, one could 
predict that the fault is around the ninth tile from the start (594/66=9). As a check, the resistance at 
the end should be about 462Ω since the fault is 7 tiles from the end (462/66=7). 
 
In other cases, it may be necessary to progressively remove tiles until the fault disappears. As in the 
open  circuit  testing  above  the  easiest  way  may  be  to  remove  the  middle  tile  and  test  each  half 
circuit, then remove the middle tile of the affected half, and so on, repeatedly dividing the circuit in 
half until the fault has been located. 
 
 

6.5  Repair and Test 

 
Once the failure has been found it can be repaired. If the fault concerns wiring or connectors it can 
often be repaired in situ. If a tile has been damaged this may be visible in the form of burning. The 
tile should be replaced, and spares are available from Lasermet. You will need to advise the size of 
tile required when ordering. 
 
Once  the  repair  has  been  affected,  the  system  should  be  restored  to  normal  operation.  With  the 
power turned on, reset the fault latch as described in Fault Latch Reset above and confirm that the 
green  Ready  light  is  illuminated  on the  Monitor  and  Detection  board  or on  the  front  panel  of  the 
interlock  controller. Ensure  any other  interlocks  (e.g. doors, covers etc.)  are  closed. Press  the  Arm 
Laser button and confirm that the interlock controller arms successfully. 

Summary of Contents for Laser Jailer

Page 1: ...Laser Jailer Maintenance Manual 00892 53 000 Issue 2 30 January 2020 LASERMET LASER JAILER ACTIVE LASER GUARDING SYSTEM INSTRUCTION MANUAL INSTALLATION MAINTENANCE AND REPAIR MANUAL Issue 2 ...

Page 2: ...ation 5 3 1 Laser Jailer Tile Description 5 3 2 Laser Jailer Tile Fixing 5 4 Wiring 6 5 Monitoring and Detection Circuit 8 5 1 General 8 5 2 Fault Latch 9 5 3 Real Time Fault Indications 11 6 Fault Location 12 6 1 Self Recovery 12 6 2 Equipment 12 6 3 Narrowing Down the Faulty Section 13 6 4 Identifying the Fault 13 6 5 Repair and Test 14 7 Warranty 15 8 Contact Details 16 ...

Page 3: ...chnicians should be aware that the Monitor and Detection board generates up to 36V with respect to earth which may be felt on contact The technician must ensure that any laser that may be connected to the interlock system is disabled so that it cannot be operated despite the interlock controller being armed Preferably this means isolating it from its power supply and ensuring that no one will reco...

Page 4: ...s control of illuminated signage override facility door locking and so on The ICS is usually connected to the interlock connector on the laser or to a beam shutter so that the ICS can disable the laser beam if the enclosure is breached In the case of Laser Jailer if a powerful laser beam misses its target and hits a detection tile on the enclosure wall it is detected by the monitoring circuit whic...

Page 5: ...wed to the mounting surface with M4 screws and 20mm tall spacers the gap behind being used for the interconnection leads between the tiles The tiles should always be screwed into place Adhesives and tapes should not be used as a tile which becomes detached may fall and cause injury For small enclosures which may be made of sheet metal the spacers may be fitted directly into the enclosure wall For ...

Page 6: ...as sockets for up to six groups of tiles and it is usual to allocate one socket to each surface of the enclosure i e one socket for the roof one for the floor one for the left wall etc Wire links are fitted across any unused connectors so that a complete circuit is formed The illustration on the left shows the wiring schematic for a simple installation with an enclosure which has two protected sur...

Page 7: ...atively be used for convenience For very large enclosures patch panels are sometimes used which allow large surfaces to be sub divided into smaller groups Such enclosures may contain a thousand or more tiles With so many tiles it may be hard to visually spot a damaged one so by dividing the surfaces into smaller groups of tiles it is easier to locate a damaged tile electrically Lasermet supply pat...

Page 8: ... circuits may be broken due to laser damage and this is also detected The same applies should a connection fail between tiles The circuit will also detect any electrical leakage to earth which might be caused for example if the insulation on a cable becomes damaged or if water ingress occurs Prior to arming the interlock controller the Monitor and Detection circuit is put into Test mode In this mo...

Page 9: ...he system to be repaired before it can be re used For example in some situations a user may attempt to electrically bypass a damaged tile in order to get the laser working again However this presents a hazard because a tile is now not monitored so part of the enclosure is not protected The fault latch keeps the interlock disabled if a tile is bypassed and unless configured otherwise even if the po...

Page 10: ...Laser Jailer Maintenance Manual 00892 53 000 Page 10 of 16 Issue 2 30 January 2020 Figure 6 Loop Open and Fault Latched indications ICS 5 and ICS 6 Figure 7 Loop Open Fault ICS 15 ...

Page 11: ...of the Fault latch as follows J8 J9 Enable Fault Latch The latch is disabled if the links are removed J10 J11 Auto Fault Reset If the links are fitted the latch can be reset by cycling the system power as described above If an external keyswitch or other control is provided to reset the latch it is connected in place of the jumpers on J10 and J11 and it should connect each pair of pins together mo...

Page 12: ...y be used to locate a fault in the tiles or interconnections Sometimes the damaged tile will be obvious Other times the damage might be difficult to see or there may be some other fault which is stopping the system from working A multimeter will be very useful Lasermet can also supply a handheld probe that can be used to locate faults A dummy tile can be made which is useful for substituting secti...

Page 13: ...al cable socket by socket until the faulty section has been identified The plugs may be inserted in any order for test purposes For example the cables for panel 2 may be inserted into the panel 3 socket etc 6 4 Identifying the Fault Once the faulty cable has been located the actual faulty part needs to be found Turn off the Interlock Controller With the cable unplugged from the Monitor and Detecti...

Page 14: ...tween one circuit and earth If the failed resistance test indicates a low value e g less than about 5kΩ and the reading is steady there could be an actual short circuit and its position can be predicted based on the theory that each tile adds 66 ohms to the resistance For example if the reading was 594Ω from the start one could predict that the fault is around the ninth tile from the start 594 66 ...

Page 15: ...fects in workmanship for 12 months Damage or defects caused by other factors are not covered For example industrial contamination incorrect cleaning storm damage Consequential loss is not covered under warranty Compensation for indirect or direct loss or damage is expressly excluded Rectification of the defects or a replacement does not initiate a new warranty period For all deliveries payments an...

Page 16: ...provide a complete system We also supply equipment and consultancy covering all aspects of laser safety Full support design and installation is available from Lasermet please contact us for any queries For sales and technical support Lasermet Ltd Lasermet House 137 Hankinson Road Bournemouth BH9 1HR United Kingdom Tel 44 0 1202 770740 Fax 44 0 1202 770730 Email sales lasermet com Website www laser...

Reviews: