Concept 

 
Suitable  for  internal  doors,  this  maglock  has  an  aluminium  finish  and  it  is  monitored  so  that  the 
status of the door locking mechanism can be confirmed. 
 
When the maglock is energised and the door is closed, the onboard relay is closed and a green LED 
illuminates. 
 
When the maglock is energised and the door is NOT closed, the onboard relay is open and a red LED 
illuminates. 
 
Lasermet  provides  a  full  range  of  laser  interlock  equipment  including  control  systems,  interlock 
switches,  illuminated  warning  signs,  laser  shutters,  door  locks,  external  power  supplies  etc.  which 
can be connected to provide a complete laser interlock system. Full support, design and installation 
is available from Lasermet, please contact us for any queries. Contact details are given at the end of 
this manual. 
 
 

Installation 

 
Handle  the  equipment  with  care,  damaging  the  mating  surfaces  of  the  magnet  or  armature  plate 
may reduce locking efficiency. 
 
The  magnet  mounts  rigidly  to  the  door  frame,  the  armature  plate  mounts  to  the  door  with  the 
hardware  kit  provided.  This  allows  it  to  pivot  about  its  centre  to  compensate  for  door  wear  and 
misalignment. 
 
The template must be used when the door is in the closed position. 
 
Before installing, add thread locker to all screws. Firmly tighten screws. 
 

NOTE:

  Fix the armature plate lightly to ensure the rubber washer remains flexible. This enables the 

armature plate to automatically adjust to its correct position with the magnet. 
 

 

Typical Installation 

Summary of Contents for MONITORED MAGLOCK

Page 1: ...Monitored Maglock Instruction Manual CEB00XXX 53 000 Issue 2 13 January 2020 LASERMET MONITORED MAGLOCK INSTRUCTION MANUAL MONITORED MAGLOCK INSTALLATION Issue 2 ...

Page 2: ... Manual CEB00XXX 53 000 Page 2 of 8 Issue 2 13 January 2020 LASERMET Maglock Instruction Manual Contents 1 Safety Warnings 3 2 Concept 4 3 Installation 4 3 1 Mounting 5 4 Wiring 6 5 Specifications 7 6 Warranty 7 7 Contact Details 8 ...

Page 3: ...made to tamper with the parts open them or use them outside of the parameters contained herein The units are only designed to be fixed to surfaces using their inbuilt fixing holes They must not come into contact with each other or any other moving part when in use The parts should never be subject to impact or mechanical strain Safety switches should never be defeated or bypassed It is imperative ...

Page 4: ...ected to provide a complete laser interlock system Full support design and installation is available from Lasermet please contact us for any queries Contact details are given at the end of this manual 3 Installation Handle the equipment with care damaging the mating surfaces of the magnet or armature plate may reduce locking efficiency The magnet mounts rigidly to the door frame the armature plate...

Page 5: ... one 1 rubber washer sandwiched between two 2 steel washers STEP 3 Install the mounting plate Adjust the mounting plate so that it and the armature plate form a right angle Using the mounting plate as a template drill the wire hole Drill and install the remaining mounting screws STEP4 Fix the magnet to mounting plate with two m4 m6 screws supplied STEP 5 Install electrical wiring per instructions ...

Page 6: ...o V Check jumper for 12VDC operation 24VDC Input Required Power 0 25A minimum Connect the positive lead from a 24VDC power source to V Connect the ground lead from a 24VDC power source to V Check jumper for 24VDC operation Contacts Relay dry contacts are rated at 1A at 24VDC for safe operation Do not exceed this rating For a normally open switch connect the wires from the system to COM and NO For ...

Page 7: ...nty Lasermet provide a 12 month warranty for defects in materials and manufacture from the date of installation or delivery Installations completed by Lasermet are covered against defects in workmanship for 12 months Damage or defects caused by other factors are not covered For example industrial contamination incorrect cleaning storm damage Consequential loss is not covered under warranty Compens...

Page 8: ...to provide a complete system We also supply equipment and consultancy covering all aspects of laser safety Full support design and installation is available from Lasermet please contact us for any queries For sales and technical support Lasermet Ltd Lasermet House 137 Hankinson Road Bournemouth BH9 1HR United Kingdom Tel 44 0 1202 770740 Fax 44 0 1202 770730 Email sales lasermet com Website www la...

Reviews: