TERMO-VIOLA
50
- check the connection of the power cable and switching to ON/1 of the switch located on the back of the stove.
- check opening of the delivery and return shutoff valves as well as the water circuit pressure.
- At first startup, remove all the components (instructions/label) that could burn from the stove firebox and
glass.
- Any lightings done after long stove idle periods require the renewal of any pellets that have been inside
the hopper for a long time, in being a damp fuel no longer suitable for combustion, and complete
cleaning of the combustion chamber.
4.3.2 Startup stage
To light the stove, press the button ‘P4’ for 3 seconds: the message ‘START’ will appear on the display.
The stage is automatic and managed entirely by the electronic controller without the possibility of changing the
parameters.
The stove carries out the startup stages in sequence according to the procedures defined by the parameters that
manage levels and times, reaching the work condition unless anomalies or alarms occur, according to the following
table:
After a certain time has elapsed, if the fume temperature has not reached the minimum permissible value the stove
goes in alarm status.
- Do not use flammable liquids to light the stove.
- In case of persistent failed lighting, contact the Service Centre.
As an alternative it is possible to switch-on the stove if you press the buttons P4 and P5 at the same time for 3
seconds. è possibile accendere la stufa premendo contemporaneamente il pulsante P4 e P5 per 3 secondi. On the
display it will appear
“Waiting for request”. In this way the stove is in stand-by and it starts again only when it
recognises a demand for warming the ambient or the sanitary water (if available).
Clock
Dialogue box
Water temperature
Room temperature
Button ‘P4’
Status
Duration
Devices
Conditions for going to next status
Igniter
Fume
exhaust
Auger
Exch.
After time Pr40
After time Pr41
After time Pr41
Fume temperature > Pr13
After after time Pr02
Room temperature < SET temperature
Fume temperature < Pr14
Room temperature < SET temperature
Water temperature < water SETTING
Fume temperature < Pr14
Every Pr03
ON/OFF to switch off
(*) Pr39 Starts from when fume T.< Pr13
OFF
START – CLEANING
PELLET PREFILL
WAITING FLAME
PELLET LOAD
WORK
MODULATES WORK
BRAZIER CLEANING
WORK
FINAL CLEANING
FIRE PRESENT