14
Each and every STRATA_HEAT™ Wire loose heating cable is subjected to careful testing before it is shipped from the factory.
However, damage does sometimes occur in storage or transit, and sometimes during
installation. We strongly recommend
you test your heaters:
After unpacking them but before you install them,
and
After you have installed them but before you install the floor
covering (i.e. while the cables are still exposed),
and
After installation of the final floor covering.
Complete a simple visual inspection of the heating cable to make sure there is no visible damage.
A simple electrical inspection can be done with a digital ohmmeter to ensure the ohms resistance is what it should be. The ohm
resistance should be measured between the two conductors without touching the yellow-green wire, which is the ground connection.
Checking for resistance between the two conductor wires ensures there is no break in the cold lead conductor and the heat resistance
wire. It does not assure you that there is no electrical short in the circuit.
Place one probe on the black wire. Place the other probe on the yellow (red wire for 240V).
Resistance can vary significantly depending on the ambient temperature and an allowance of +/- 5% from the norm is
acceptable.
Ensure cable is fully insulated:
Test across the yellow-green wire (ground). Place the other probe on the yellow (red wire for 240V ).
Confirm the reading is infinity (open circuit).
Repeat these steps to check the reading between the yellow-green wire (ground) and the black wire.
There should be no continuity between these wires and the ohms reading should be infinity (not zero). If your meter shows a number of
ohms between these wires, your heating cable has an electrical short. Take note of the resistance and contact LATICRETE.
In order to conduct a more thorough test for insulation verification, LATICRETE recommends the use of a megohmeter. Connect the
instrument’s black cable to the system’s ground and the red to the either one of the heating cable leads.
Note that depending on your meter model, you may read “kilo-Ohms” probably due to your fingers touching the probes (it’s your
body’s conductivity). If the readings are not satisfactory, do not commence installation contact LATICRETE for further advice.
TESTING THE SYSTEM
Summary of Contents for STRATA_HEAT 0802-0017-2
Page 11: ...11 WIRING DIAGRAM 120V...
Page 12: ...12 WIRING DIAGRAM 240V...
Page 22: ...22 NOTES...
Page 24: ...24 FLOOR PLAN...
Page 26: ...26 NOTES...
Page 27: ......