17
INSTALLING THE FLOOR SENSOR
The floor sensor is used for temperature regulation of the floor surface. The
end of the probe wire contains a capped sensor that should be centered
between two heating cables at least 12" (305 mm) into the heated area.
The sensor wire
MUST NOT
touch or cross over the STRATA_HEAT™ Wires.
Depending on the requirements of the tiler, it may be necessary to chisel out
short channels in the subfloor to minimize the increased height presented
by the floor probe. Before chiseling the area, ensure that the STRATA_HEAT
Wire, unheated lead and floor probe are protected to avoid damage during
chiseling. Place the floor probe into the channels and secure with fixing tape.
NOTE: Do
NOT
run the cold lead wires and the floor sensor in the same conduit.
Installing the STRATA_HEAT
™
Thermostat
Instructions for the fitting of the STRATA_HEAT Thermostat can be found inside the thermostat box. Each cable has one unheated lead.
Please review the information on pages 10 through 13 before proceeding.
The protective ground wire leading from the unheated lead should be connected to the ground leading from the power supply.
IMPORTANT! Test the STRATA_HEAT™ Wire
Before installing the final floor finish ensure that the STRATA_HEAT™ Wire
is working properly using the method described on page
14.
Test the probe wire:
Temperature sensor wire must be verified before and after installation.
For probe resistances, refer to the STRATA_HEAT Thermostat instructions.