38 / 124
ECO Silver
Suitable cooling water quality
Specification
Value and Unit
pH – value
7.5 – 9.0
Hydrocarbonates [HCO
3
-]
70 – 300 mg/L
Chlorides (Cl
-
)
< 50 mg/L
Sulfates [SO
4
2-
]
< 70 mg/L
Hydrocarbonates [HCO
3
-] / sulfates [SO
4
2-
]
> 1.0
Total hardness
4.0 – 8.5 °dH
Conductivity
30 – 500 μS/cm
Sulfites [SO
3
2-
]
< 1 mg/L
Free chlorine gas (Cl
2
)
< 0.5 mg/L
Nitrates (NO
3
-)
< 100 mg/L
Ammonia (NH
3
)
Not permissible
Iron (Fe), dissolved
< 0.2 mg/L
Manganese (Mn), dissolved
< 0.05 mg/L
Aluminum (Al), dissolved
< 0.2 mg/L
Free aggressive carbonic acid (CO
2
)
Not permissible
Hydrogen sulfide (H
2
S)
Not permissible
Algae growth
Not permissible
Suspended matter
Not permissible
Risk to the environment due to oil contamination of the cooling water circuit
With a leaky condenser there is the danger that refrigerating machine oil from the refrigerant circuit of the cooling thermo-
stat can pass into the cooling water.
Follow all the legal requirements and the regulations of the water supply utility which apply at the point of use.
Water pollution due to leakage
To avoid pollution due to a leak in the cooling water system it is recommended that a leakage-water detector with a water
cut-off is installed.
Servicing intervals
Follow the information for cleaning and decalcifying the cooling water circuit (
Summary of Contents for ECO Silver E 10 S
Page 1: ...ECO Silver Operation manual ...
Page 2: ......
Page 4: ......
Page 78: ...78 124 ECO Silver 10 2019 i ...
Page 79: ...10 2019 i ECO Silver 79 124 ...
Page 80: ...80 124 ECO Silver 10 2019 i Appendix with settings ...
Page 111: ...10 2019 i ECO Silver 111 124 5 Click on Continue installation 6 Click on the key Finish ...
Page 113: ...10 2019 i ECO Silver 113 124 ...
Page 120: ...120 124 ECO Silver 10 2019 i Blank page ...
Page 121: ...10 2019 i ECO Silver 121 124 Blank page ...
Page 122: ...122 124 ECO Silver 10 2019 i ...
Page 125: ......
Page 126: ......
Page 127: ......