8.3.4
Cleaning the condenser
8.3.4.1
Air-cooled condenser
The cooling circuit is largely maintenance-free.
Remove dust and contamination from the condenser at regular
intervals (depending on operating period and exposure conditions).
–
To do this, remove the front grille by grasping it at the
bottom with both hands and pulling the grille to the front.
To avoid damage, remove the front grille slowly and care-
fully.
–
Then brush down the condenser and, where necessary,
blow it out with compressed air.
Note:
Caution!
Contact with sharp-edged vanes on the condenser
during cleaning
Cuts
Clean the condenser with suitable tools (e.g. hand brushes,
compressed air...).
8.3.4.2
Water-cooled condenser
To obtain the full cooling output, the sieve and water circuit must be cleaned at regular intervals.
Cleaning the screw-in sieve
For regular cleaning (depending on the degree of contamination of the cooling water) screw-in sieve:
–
Remove the water supply hose from the device.
–
Unscrew the fitting from the device with a 19 AF open-ended wrench and remove the screw-in sieve from the
fitting.
–
Clean the screw-in sieve and then insert in back into the fitting.
–
Mount the fitting and the water supply hose onto the device.
Summary of Contents for ECO Silver E 10 S
Page 1: ...ECO Silver Operation manual ...
Page 2: ......
Page 4: ......
Page 78: ...78 124 ECO Silver 10 2019 i ...
Page 79: ...10 2019 i ECO Silver 79 124 ...
Page 80: ...80 124 ECO Silver 10 2019 i Appendix with settings ...
Page 111: ...10 2019 i ECO Silver 111 124 5 Click on Continue installation 6 Click on the key Finish ...
Page 113: ...10 2019 i ECO Silver 113 124 ...
Page 120: ...120 124 ECO Silver 10 2019 i Blank page ...
Page 121: ...10 2019 i ECO Silver 121 124 Blank page ...
Page 122: ...122 124 ECO Silver 10 2019 i ...
Page 125: ......
Page 126: ......
Page 127: ......