Integral XT
56
Starting up
YAWE0028 / 24/06/2016
Draining residues XT 150, XT 250 W
After draining, liquid residues may still be located in the return hose.
Proceed as follows:
1. Remove the return hose from the load.
2. Empty the residue from the hose into a con-
tainer.
7.8
Changing the heat transfer liquid and internal cleaning
After draining there are residues of heat transfer liquid in the device depending on the type of liquid was
used.
Remove these with the following cleaning procedure:
1. Connect a short-circuit hose to the outflow and return (
þ
2. Fill the device with a suitable cleaning liquid whilst operating in the filling mode (
þ
7.6).
If water with a cleaning agent (fat solvent) is used, it is essential to ensure that the device is only
operated in the filling mode (refrigerating machine is therefore off). Otherwise there is the risk that
the device may ice up internally and be damaged.
Suitable cleaning liquids
for
Acetone (solvent)
It is essential to follow the relevant safety precautions when
using acetone!
Kryo 55
Kryo 70
Kryo 85
Kryo 90
Ultra 350
Water
Kryo 30
3. Drain (
þ
7.7) and remove the short-circuit hose. Dry the device with compressed air. To do this,
carefully allow compressed air to flow into the device, alternately via the outflow and return. If
cleaning is carried out with liquids which readily dissolve oil, such as acetone, do not let the unit
stand dry or transport it dry for a longer period (more than one day), because the pump requires a
minimum lubrication. Therefore, continue with point 4.
4. After cleaning, fill with new heat transfer liquid and vent (
þ
5. If contamination is still found (remove 0.5 liters with draining program (
þ
7.7)), it is recommended
that the new heat transfer liquid is again changed and cleaned externally, or the residues of the
old heat transfer liquid are separated.
+
If residues of an old heat transfer liquid are not removed and remain in the device and
the device is then operated above the thermal loading limit for this heat transfer liquid,
deposits may form, particularly on the heaters, which reduce the performance capacity
of the device or even reduce the service life of the device.
Summary of Contents for Integral XT 150
Page 2: ......
Page 4: ......
Page 164: ...Integral XT 162 YAWE0028 24 06 2016 Intentionally left blank ...
Page 166: ......
Page 167: ......