Integral XT
122
Interface modules
YAWE0028 / 24/06/2016
Contact inputs and outputs
−
View of the socket from the plug side or of the plug on the solder
side.
−
A suitable 15-pole Sub-D plug can be obtained together with a
suitable housing:
Order no. EQM 030 and plug housing order no. EQG 017.
8.5.2 Namur-Contact module LRZ 914 with only one input and one output
Contact module (order no. LRZ 914) with connector to NAMUR NE28. Functionality as LRZ 915, but only
one output and one input on each of two DIN sockets.
Contact inputs and outputs:
Output
Input
−
View on flange plug (Front) or solder side
coupler socket.
−
Max. 30 V; 0.2 A.
Coupler socket order no. EQD 047.
−
View on flange plug (Front) or solder side
coupler socket.
−
Signal ca. 5 V, 10 mA. Do not use pin 3!
Coupling plug order no. EQS 048.
1 = n.o. (make)
2 = common
3 = n.c. (break)
+
Use shielded lines. Connect shielding with connector housing. Cover unused plug con-
nections with protecting caps!
5V
1 Input
1 Output
Contact module LRZ 914; DIN sockets
2 1 3 1 2
1
5V
Input
Output
1 2 3
Contact module LRZ 915; SUB-D
12 4 5 6 13 14 15 7 8
2
5V
3
5V
1 9 2 10 3 11