Integral XT
YAWE0028 / 24/06/2016
Starting up
91
−
Week plan
à
Arrange
takes you to
the window shown on the left.
−
Using the cursor keys
,
select the
field which is to be filled in.
−
Open the input dialog of the field with
: Select a time in the time fields and
an action in the action field.
−
In the example on the right the thermo-
stat is started on Monday at 7:30h, Pro-
gram 4 is executed at 10:00h on Tues-
day and the standby mode is switched in
on Friday at 16:00h. Fields displaying
“------” are passive.
Confirm each field selection with
or quit
with
without making changes.
The menu
Action
is used to define
what
is
to be carried out:
−
Start
activates the thermostat from the
standby mode.
−
Standby
activates the standby mode
(refrigerating unit, heater and pump are
switched off).
−
Program X
all actions of this program
defined in the programmer are pro-
cessed.
7.15 Control and Control parameters
The control parameters are optimized ex-works for operation as a process thermostat. The parame-
ters are also preset for the operation with external control. Sometimes however, the operation of ex-
ternal containers requires adaptation. Also the thermal capacity and viscosity of the heat transfer liquid
sometimes require adaptation.
+
−
The intelligent menu guidance with the Master and Command detects whether you
have set the device (as described in Section 7.9.6), to internal or external control
and only displays the relevant dialog boxes in each case.
−
Some control parameters are automatically optimized by your Integral XT process
thermostat. This automatic mechanism should only be deactivated and manually
optimized in exceptional cases.
In order to obtain good control characteristics, the hydraulic system should provide the best possible
coupling of the object to be temperature stabilized to the thermostatic device. The following should be
fulfilled in this respect:
Week plan
Time Action Time Action
Monday
07:30 Start
17:00 -------
Tuesday
10:00 Prog.4 17:00 -------
Wednesday 08:00 -------
17:00 -------
Thursday
08:00 -------
17:00 -------
Friday
08:00 -------
16:00 Standby
Saturday
08:00 -------
17:00 -------
Sunday
08:00 -------
17:00 -------
Pump Menu
End
T
set
T
fix
Pump Menu
End
T
set
T
fix
Start
Standby
Program 1
Program 2
Program 3
Program 4
Program 5
Status
Function
Action
Set time
Set date