The case height is 140 mm higher for the VC 1200 (W) and VC
2000 (W) devices with the more powerful pump.
Device
Clearance around the
device
Exhaust air (air-
cooled devices)
cm (front/back/right/left)
m³/h
VC 1200
20/20/20/20
650
VC 1200 W
20/20/0/0
---
VC 2000
20/20/20/20
650
VC 2000 W
20/20/0/0
---
VC 3000
50/50/20/20
1300
VC 3000 W
20/20/0/0
---
VC 5000
50/50/20/20
2500
VC 5000 W
20/20/0/0
---
VC 7000
50/50/20/20
4500
VC 7000 W
20/20/0/0
---
VC 10000
50/50/20/20
4500
VC 10000 W
20/20/0/0
---
Tab. 12: Power consumption VC 1200 (W) to VC 3000 (W)
Alternating current
VC 1200 (W)
VC 2000 (W)
VC 3000 (W)
Unit
230 V; 50 Hz
1.1
1.6
1.8
kW
200 V; 50/60 Hz
1.3
2.0
2.2
kW
208–220 V; 60 Hz
1.4
2.2
2.3
kW
Tab. 13: Power consumption VC 5000 (W) to VC 10000 (W)
Three-phase current
VC 5000 (W)
VC 7000 (W)
VC 10000 (W)
Unit
400 V; 3/N/PE~50 Hz
3.3
4.3
5.4
kW
208-220 V; 3/PE~60 Hz
3.6
4.6
5.9
kW
200 V; 3/PE~50/60 Hz
3.5
4.5
5.7
kW