TROUBLES
CAUSES
SOLUTIONS
1 1 THE GENERATOR
PRESSURE DOES NOT
INCREASE
1- Pressure switch
1-Burner
1-Resistance temperature
detector PT100
1-Check the pressure
switch
1-Check electrodes, diesel
nozzle
1-Check that the tempera-
ture is at least 150°C
- Authorized After Sales
Service
- The user
- The user
2 2 THE PUMP CANNOT
RUN
2.1 It loads no water
2.1 Pump
2.1 Clogged filter
2.1 Replace the pump
2.1 Clean the filter
- Authorized After Sales
Service
- The user
3 THE SAFETY VALVE
OPENS REPEATEDLY
3.1 It keeps on
loading water
3.1Boiler water level probe
3.1Pressure switch
3.1Safety valve
3.1Clean the probe dischar-
ging boiler pressure
3.1Replace the pressure
switch and check that the
connection discharging
tube is free from incru-
stations.
3.1Replace the safety valve
- Authorized After Sales
Service
- Authorized After Sales
Service
- Authorized After Sales
Service
The safety valve can be
replaced only by or qua-
lified service center.
Safety valve replacement
must be set at 12 bar
and be accompanied
by certified PED as provi-
ded for category IV
EN
21