Operating Instructions – LBAT10/20/PMR – Version 2017
25
•
Red and green display LEDs (terminals 10 to 15) (already connected):
The red and green display LEDs are used to display the turnstile’s current status in each direction of
passage. They have 3 possible states:
o
Solid red:
turnstile locked in the corresponding direction (awaiting an access
command)
o
Solid green:
turnstile unlocked in the corresponding direction (an access
command has been taken into account)
o
Flashing red:
turnstile not back in position (no access command will be taken
into account)
•
Passage information reports (terminals 16 to 19):
Passage reports are NO dry contacts that close for 0.5 s when the turnstile rotates beyond 60°, the
angle after which the user can no longer pass back through. The customer must use these two contacts
for its access control to count the number of passages or perform an anti “pass-back”.
•
Dusk-to-dawn switch (terminals 41 to 46) (option):
A dusk-to-dawn switch can be connected to manage the intensity of the roof’s LEDs based on the
luminosity.
•
Power supply (terminals N and Ph):
The supply cable must be wired last to avoid all electrical risks.
It must be type 3G 1.5 mm
2
or 2.5 mm
2
(depending on the cable distance).
Provide electrical protection at head-end (differential circuit breaker 10A-30 mA/turnstile)
The power cable earth must without fail be connected to the earth strip next to the terminal board.
Once installed, the turnstile must be powered to prevent any inside condensation