background image

GB-9

D

GB

F

NL

I

E

 

When heating up for the first time, for example, 
vapours may be emitted from seals or coatings 
which may cause unpleasant odours.

  

  All valves of the installation must be checked for 

tightness before ignition.

Coarse adjustment with the furnace cold

 

Coarse adjustment of the air volumes, see 
page 6 (Preparing commissioning).

  

 Limit the maximum gas volume.

 

Open the restrictor around halfway.

  

 Open the gas supply.

 4 

 Ignite the burner.

 

The safety time of the automatic burner control 

unit starts to elapse.

 5 

 Check and adjust the gas and air pressures.

 6 

  If no flame is formed, reset the automatic burner 

control unit, purge the combustion chamber and 
ignite the burner again.

 

The burner ignites and proceeds to normal op-

eration.

 

 If no flame is formed after repeating steps 

5

 and 

6

 multiple times – see page 13 (Assistance in 

the event of malfunction).

 7 

  Check the differential pressures ∆p

gas

 and ∆p

air

 

and the negative flue gas pressure p

FG

, and set 

them to their desired values.

 

The gas, air and motive air settings affect each 

other. We recommend reading these pressures 
at the same time.

 

Check the settings by conducting a flue gas 
analysis (in the flue gas connector in the case of 
an indirect heating system or in the furnace in the 
case of a direct heating system). Ensure that the 
furnace pressure is positive for a direct heating 
system to avoid falsification of the measurements 
by infiltrated air.

Tightness test

 DANGER

To ensure that there is no danger resulting from a 

leak, check the gas connections on the burner for 
leaks immediately after the burner has been put 
into operation.

8

Fine adjustment with a hot furnace

 

Final adjustment of the burner should be carried 
out at maximum furnace temperature and high 
capacity demand.

 9 

 Heat the furnace. 

 0 

 Watch the furnace pressure and O

2

 value in the 

furnace atmosphere. Avoid negative pressure 
and substoichiometric operation of the burner. If 

necessary, adjust the settings of the combustion 
air and motive air.

  

 Check the differential pressures ∆p

gas

 and ∆p

air

 

and the negative flue gas pressure p

FG

 at max. 

furnace temperature, and adjust them using the 
appropriate restrictor.

p

0

p

2

p

1

 

Check the settings by conducting a flue gas 
analysis (in the flue gas connector or eductor in 
the case of an indirect heating system or in the 
furnace in the case of a direct heating system). 
Ensure that the furnace pressure is positive for 
a direct heating system to avoid falsification of 
the measurements by infiltrated air.

 DANGER

Risk of explosion and poisoning in case of 
burner adjustment with an air deficiency!

 Ad-

just the gas and air supply so that the burner is 
always operated with excess air – otherwise CO 

will form in the furnace chamber. CO is odourless 
and poisonous! Conduct a flue gas analysis.

  

 Watch the furnace pressure at high capacity 

demand and various furnace temperatures to 
optimize the motive air setting. 

 

The furnace pressure should be slightly posi-

tive in all operating states (0.1 to 0.3 mbar). 
If the positive pressure exceeds approx. 
0.3  mbar, increase the flue gas extraction 
rate to prevent the burner being damaged. 
If there is a negative pressure in the furnace 
chamber, reduce the flue gas extraction rate to 
avoid infiltrated air.

Blocking and recording the settings
  

 Produce a measurement report.

 4 

 Remove the measuring devices and close off 

the test nipples – tighten the grub screws.

 5 

 Block and seal the adjusting elements.

 6 

  Induce a flame failure, e.g. by pulling the plug off 

the ionization electrode. The flame detector must 
close the gas safety valve and signal a fault.

 7 

  Switch the system on and off several times while 

monitoring the automatic burner control unit.

 8 

 Produce an acceptance report.

 DANGER

An incorrect change of the burner settings may 

change the gas/air ratio and lead to unsafe oper-
ating conditions. Risk of explosion in case of CO 
being formed in the furnace chamber! CO is odour-
less and poisonous!

Summary of Contents for ECOMAX Series

Page 1: ...s technicians Electrical interventions may only be carried out by qualified electricians Wear protective clothing for all installation and maintenance work to prevent injuries Conversion spare parts A...

Page 2: ...2 P03 Gas flange with purging air connection K3 Additional cooling air connection A3 Kanthal electrode DA13 DA23 Differential air pressure measuring kit Differential air pressure measuring kit with pr...

Page 3: ...it D and the eductor EJEK are re quired see page 14 Accessories EJEK FGT kit D EJEK 1 Remove the transport safety device If the diameter of the furnace insulation is greater than the external diameter...

Page 4: ...flange and SER M Install the internal segmented flame tubes SICAFLEX see www docuthek com Elster Kromschr der Kromschr der LBE Prod ucts 07 Pilot burners and burners Self recuperative burner ECOMAX S...

Page 5: ...this pur pose see page 10 Replacing the gas lance If necessary another air connection may be used The burner has three air connections two of which are sealed with blind flanges Ensure undisturbed fl...

Page 6: ...particular avoid external electrical interference when using ionization control For UV control route the ignition cable separately from the UV cable 1 3 2 4 Connect the PE wire for grounding to the g...

Page 7: ...s are installed in the gas and combustion air connections on the burner Adjustment is made on the basis of the flow rate dependent pressure differential The required pressure differentials for gas and...

Page 8: ...ative flue gas pressure on the motive air restrictor Pressure switch If the burner is equipped with a pressure switch on the air connection to monitor the flow the switching point should be set to app...

Page 9: ...substoichiometric operation of the burner If necessary adjust the settings of the combustion air and motive air 11 Check the differential pressures pgas and pair and the negative flue gas pressure pF...

Page 10: ...ast 5 A and must not vary Read off the ionization signal on the burner con trol unit 3 Disconnect the system from the electrical power supply 4 Shut off the gas and air supply do not change the restri...

Page 11: ...procedure when reassem bling We recommend that the burner be removed to allow a more accurate inspection 26 27 If the insulation is worn or damaged it must be replaced Checking replacing the air guide...

Page 12: ...nsu lation together e g using adhesive tape Tighten the nuts in two cycles in a crosswise fashion 40 41 Tighten the nuts in two cycles in a crosswise fashion Torque for ECOMAX 1 3 18 Nm ECOMAX 4 5 35...

Page 13: ...s detected when checking the burner proceed to the automatic burner control unit and check for faults in accordance with the relevant operating instructions Faults Cause Remedy Burner does not functio...

Page 14: ...gs Check the gas and air pressures Automatic burner control unit signals a fault Check the ionization cable Check the ionization current The ionization cur rent must be at least 5 A stable signal Mixi...

Page 15: ...t Eco 2 5 E 22801111 P2 set Eco 4 0 E 22801108 P3 set Eco 2 5 B 22801107 P3 set Eco 4 0 B 22801106 Technical data Heating direct with eductor or indirect in radiant tube Control type On Off Control ra...

Page 16: ...C Annex II No 1B The product Self recuperative burner for gas ECOMAX is a partly completed machine pursuant to Article 2g and is designed exclusively for instal lation in or assembly with another mach...

Page 17: ...GB 17 D GB...

Page 18: ...8 0 F 49 202 60908 20 GB 18 GB F NL I E Contact If you have any technical questions please contact your local branch office agent The addresses are available on the Internet or from Elster GmbH We res...

Reviews: