3
1.3 Specification
Model
DP1OL-3KTRL-120
Capacity
3kVA/3kW
Input
Nominal Voltage
100/110/115/120/127VAC, L+N+PE
Voltage Range
55-150VAC
Frequency
40-70Hz
Power Factor
�
0.99
THDi
≤4% (linear load); ≤5% (non-linearload)
Output
Nominal Voltage
100/110/115/120/127VAC, L+N+PE
Voltage Regulation
±1%
Frequency
50/60Hz±0.1%
CrestRatio
3:1
Voltage HarmonicDistortion
≤2% (linear load); ≤4%
�
non-linear load
�
Transfer Time
Line modeto battery mode,0ms;inverter to bypass,4ms(typical)
Waveform
Pure sine wave
Overload time
Line mode:
10min@102%-110% load
1min@110-130%load
10s@130%-150%load
Battery mode:
1min@102%-110% load
10s@110-130%load
30s@130%-150%load
Efficiency
Line Mode
94%
Battery Mode
93%
ECOMode
98%
Battery
Type
Sealed lead acid maintenancefree
Voltage
96VDC
Battery Number
12V 9Ah*8pcs
ChargingCurrent
1A
ChargingMode
Two/Threeperiod charging
Management
Intelligent port
RS232/USBport/SNMP card (optional)/Dry contact kit (optional)
Environment
Operation Temperature
0-40℃
Relative Humidity
0-95%(non-condensing)
Audible Noise
�
40dB@1 meter
Altitude
The altitude should not exceed 1000m,and the height above 1000m
should be reduced to a maximumof 4000m.Refer to IEC 62040