4
Loadat highaltitude=Rated power *Derating factor (correspondingto altitude)
Altitude(m)
1000
1500
2000
2500
3000
3500
4000
4500
5000
Derating factor
100%
95%
91%
86%
82%
78%
74%
70%
67%
Notice: If the machine is used at above 1000m,diminishing ratings output must be used,
please refer to above table for derating factor.
1.4 Electromagneticcompatibility
Safety
IEC/EN 62040-1-1
EMI
ConductedEmission
……
IEC/EN 62040-2
ClassA
Radiated Emission..........IEC/EN 62040-2
ClassA
EMS
ESD................................... IEC/EN 6100-4-2
Level 4
RS.....................................IEC/EN 6100-4-3
Level 3
EFT....................................IEC/EN 6100-4-4
Level 4
SURGE..............................IEC/EN 6100-4-5
Level 4
Low FrequencySignals
……
IEC/EN 6100-2-2
Warning:
Thisis aproduct for commercialand industrial application in the second
environment-installationrestriction or additional measuresmaybe needed to prevent
disturbances.
NOTICE:
Thisis aproductfor restricted sales distribution to informedpartners. Installation restrictions
or additional measuresmaybe needed to prevent radio interference.
Operate the UPS in an indoor environment only in an ambient temperature range of 0-40
℃
(32-104
℉
). Install it in a clean environment, free from moisture,flammableliquids, gasesand
corrosive substance.
ThisUPS contains nouser-serviceableparts exceptthe internal battery pack.The UPS ON/OFF
pushbuttons donot electrically isolate internal parts. Under no circumstanceattempt to gain
accessinternally, due to the riskof electric shockor burn.
Donot continue to usethe UPS if the panel indicationsare not accordancewith these
operatinginstructions or the UPS performancealters in use. Reflect all faults to your dealer.
Servicing of batteries shouldbe performed or supervised bypersonnel knowledgeableof
batteries and the precautions.
Keepunauthorizedpersonnel away from the batteries. Proper disposalof batteries is required.
Refer to your local laws andregulations for disposalrequirement.
DONOTCONNECT
equipmentthat could overload the UPS or demand DCcurrent from the
UPS, for example:electric drills, vacuumcleaners, laser printers, hair dryer or any appliance
usinghalf-waverectification.
Storing magneticmedia ontop of the UPS mayresult in data lossor corruption.
Turnoff and isolate the UPS before cleaningit. Use only a dry cloth, never liquid or aerosol
cleaners.