20
J3-2
TEMP_COM
Common terminal for temperature detection
J4-1
REMOTE_EPO_NC
Trigger EPO when disconnect with J4-2
J4-2
+24V_DRY
+24V
J6-1-1
BCB Drive
Output dry contact, function is settable.
Default: Battery trip signal
J6-1-2
GND_DRY
Ground for +24V
J6-2-1
BCB_Status
Input dry contact, function is settable.
Default: BCB Status and BCB Online, (Alert no battery
when BCB Status is invalid).
J6-2-2
GND_DRY
Ground for +24V
J7-1
BCB_Online
Input dry contact, function is settable.
Default: BCB Status and BCB Online (Alert no battery
when BCB Status is invalid)
J7-2
GND_DRY
Ground for +24V
J8-1
BAT_LOW_ALARM_NC
Output dry contact (Normally closed), function is
settable.
Default: Low battery alarming
J8-2
BAT_LOW_ALARM_NO
Output dry contact (Normally open), function is
settable.
Default: Low battery alarming
J8-3
BAT_LOW_ALARM_GND
Common terminal for J8-1 and J8-2
J9-1
GENERAL_ALARM_NC
Output dry contact, (Normally closed) function is
settable.
Default: Fault alarming
J9-2
GENERAL_ALARM_NO
Output dry contact, (Normally open) function is
settable.
Default: Fault alarming
J9-3
GENERAL_ALARM_GND
Common terminal for J9-1 and J9-2
Note
The function for each port can be set by the monitor software.
The default function of each port is described as follows.
Battery Warning Output Dry Contact Interface
The input dry contact J2 and J3 can detect the temperature of batteries and environment respectively,
which can be used in environment monitoring and battery temperature compensation.