Protect the cables - The power transmission cables must be protected from mechanical damage
and fatigue. Run the cables through an approved conduit / trunking.
Cable strain relief - Prevent mechanical strain on all cables. Cable ties or cable glands are a good
way to prevent mechanical strain on the cables.
Fuses - The DL-300 controller should be protected with a suitably rated ‘slow-blow’ DC fuse or DC
circuit breaker. Please refer to the table below for the correct rating. The fuse or breaker should be
positioned between the DL-300 and batteries (on the positive cable)
DL-300 Voltage Set Points
Whilst operating, the DL-300 does a multi-stage charge based on time and the bulk and float
voltages:
12V Set points
Mode
Flooded
Sealed
Bulk
14.6
14.3
Float
13.4
13.4
Protect
16.0
15.0
24V Set points
Mode
Flooded
Sealed
Bulk
29.2
28.6
Float
26.8
26.8
Protect
32.0
30.0
LED Indicators
Power Up (when the unit is switched on):
o
both LEDs ‘cycle’ during a self test period
Charging Mode:
o
Bulk Charge: green LED on continuous
o
Absorption Charge: green LED blink (12hz)
o
Float Charge: green LED slow flash (6hz)
o
Dumping Excess: red LED continuous when dump load active
Nominal Voltage
DC Fuse / DC Circuit Breaker Rating
12V
30 Amp
24V
15 Amp