M415B Micro Microstepping Driver Manual V2.0
Tel: +086 0755-26434369 5 Web Site: www.leadshine.com
Connections to 6-lead Motors
Like 8 lead stepping motors, 6 lead motors have two configurations available for high speed or high
torque operation. The higher speed configuration, or half coil, is so described because it uses one half
of the motor
’
s inductor windings. The higher torque configuration, or full coil, uses the full windings
of the phases.
Half Coil Configurations
As previously stated, the half coil configuration uses 50% of the motor phase windings. This gives
lower inductance, hence, lower torque output. Like the parallel connection of 8 lead motor, the torque
output will be more stable at higher speeds. This configuration is also referred to as half chopper. In
setting the driver output current multiply the specified per phase (or unipolar) current rating by 1.4 to
determine the peak output current.
Figure 5: 6-lead motor half coil (higher speed) connections
Full Coil Configurations
The full coil configuration on a six lead motor should be used in applications where higher torque at
lower speeds is desired. This configuration is also referred to as full copper. In full coil mode, the
motors should be run at only 70% of their rated current to prevent over heating.
Figure 6: 6-lead motor full coil (higher torque) connections
Connections to 8-lead Motors
8 lead motors offer a high degree of flexibility to the system designer in that they may be connected
in series or parallel, thus satisfying a wide range of applications.
Series Connections
A series motor configuration would typically be used in applications where a higher torque at lower
speeds is required. Because this configuration has the most inductance, the performance will start to
M415B Micro Microstepping Driver Manual V2.0
Tel: +086 0755-26434369 6 Web Site: www.leadshine.com
degrade at higher speeds. In series mode, the motors should also be run at only 70% of their rated
current to prevent over heating.
Figure 7: 8-lead motor series connections
Parallel Connections
An 8 lead motor in a parallel configuration offers a more stable, but lower torque at lower speeds. But
because of the lower inductance, there will be higher torque at higher speeds. Multiply the per phase
(or unipolar) current rating by 1.96, or the bipolar current rating by 1.4, to determine the peak output
current.
Figure 8: 8-lead motor parallel connections
6. Power Supply Selection
The M415B can match medium and small size stepping motors (from NEMA size 14 to 23) made by
Leadshine or other motor manufactures around the world. To achieve good driving performances, it is
important to select supply voltage and output current properly. Generally speaking, supply voltage
determines the high speed performance of the motor, while output current determines the output
torque of the driven motor (particularly at lower speed). Higher supply voltage will allow higher
motor speed to be achieved, at the price of more noise and heating. If the motion speed requirement is
low, it
’
s better to use lower supply voltage to decrease noise, heating and improve reliability.
Regulated or Unregulated Power Supply
Both regulated and unregulated power supplies can be used to supply the driver. However,
unregulated power supplies are preferred due to their ability to withstand current surge. If regulated
power supplies (such as most switching supplies.) are indeed used, it is important to have large
current output rating to avoid problems like current clamp, for example using 4A supply for 3A
motor-driver operation. On the other hand, if unregulated supply is used, one may use a power supply
of lower current rating than that of motor (typically 50%
~
70% of motor current). The reason is that