User Manual of iSV2-CAN Servo
www.leadshine.com
95
2
Enable regenerative resistance discharge
Notice
:
Pr7.32
Name
Regenerative resistance open threshold setting
Mode
P
S
T
Range
20
~
90
Unit
V
Default
80
The external resistance is activated when the actual bus voltage is higher than Pr7.32 plus Pr7.33 and is
deactivated when the actual bus voltage is lower than Pr7.32 minus Pr7.33
Notice
:
Pr7.33
Name
Regenerative resistance control hysteresis
Mode
P
S
T
Range
1
~
50
Unit
V
Default
5
The external resistance is activated when the actual bus voltage is higher than Pr7.32 plus Pr7.33 and is
deactivated when the actual bus voltage is lower than Pr7.32 minus Pr7.33
Notice
: