25
3.0 Power Supply
,
continued
745-573-B0-001 REV. A
CAUTION:
Short circuit danger: Do not rest tools or equipment on top of batteries. Do not
allow batteries to become shorted as an explosion may occur causing severe
injury. Do not open or mutilate batteries. Released electrolyte is extremely
harmful to skin and eyes. Do not dispose of batteries in fire as an explosion my
occur.
CAUTION:
Government regulations may require that batteries be recycled. See your
battery distributor for details on recycling (third-party batteries) or contact Alpha
Technologies for recycling AlphaCell
TM
battery products.
CAUTION:
Batteries shall be 12 Vdc with the same amp-hour rating. Do not mix old and
new batteries; replace batteries as a set using UL recognized batteries.
CAUTION:
Servicing of batteries shall be performed or supervised by personnel
knowledgeable of batteries and the required precautions.
Keep unauthorized
personnel away from batteries
.
CAUTION:
The following precautions shall be observed when working with batteries:
•
Follow approved OSHA (or appropriate other) regulations for handling batteries.
•
Always wear eye protection and a protective vest when working near batteries.
•
Batteries produce explosive gases. Keep away all sparks and flames.
•
Remove watches, rings or other metal objects
•
Use tools with insulated handles.
•
Wear rubber gloves and boots
Tools required
:
10mm (Lectro™) or 7/16” (AlphaCell™) socket
Inch-pound torque wrench
Multimeter
3.2
Battery Installation and Connection