26
3.0 Power Supply,
continued
745-573-B0-001 REV. A
1.
Confirm the CPR
TM
DC circuit breaker is off (down).
2.
Place the batteries in the bottom of the cabinet, negative terminals (-) at the rear of the cabinet.
3.
Connect the red battery cable which comes from the gray connector on the CPR
TM
module to the
positive (+) terminal of the left battery. Torque all connections to 60 inch-pounds (6.8 Newton-
meters).
4.
Connect the three (3) battery interconnection jumpers as shown below. Torque all
connections to 60 inch-pounds (6.8 Newton-meters).
5.
Confirm that the CPR
TM
DC circuit breaker is off (down). Connect the black battery cable which
comes from the gray connector on the CPR
TM
module to the negative (-) terminal of the right
battery. Torque connection to 60 inch-pounds (6.8 Newton-meters).
6.
Measure the DC voltage to ensure proper installation of all battery wiring. Open circuit DC voltage
should measure between 45 volts and 51 volts.
7.
Verify that the gray Anderson connector is properly attached to the left side of the CPR
TM
module.
3.2 Battery Installation and Connection,
continued
3.2.1
48V Battery Installation Procedure
+
-
+
-
+
-
+
-
CABINET FRONT
RED
BLACK
Fuse
Gray Anderson
Connector
Fig. 3-5, 48V Battery Connections – single string P/N 875-182-21