27
3.0 Power Supply
,
continued
745-573-B0-001 REV. A
1.
Confirm the CPR
TM
DC circuit breaker is off (down).
2.
Place the batteries in the bottom of the cabinet, negative terminals (-) at the rear of the cabinet.
3.
Connect the red battery cable which comes from the red and black connector on the CPR
TM
module to the positive (+) terminal of the left battery. Torque all connections to 60 inch-pounds
(6.8 Newton-meters).
4.
Connect the two (2) battery interconnection jumpers as shown below. Torque all connections to
60 inch-pounds (6.8 Newton-meters).
5.
Confirm that the CPR
TM
DC circuit breaker is off (down). Connect the black battery cable which
comes from the red and black connector on the CPR
TM
module to the negative (-) terminal of the
right battery. Torque connection to 60 inch-pounds (6.8 Newton-meters).
6.
Measure the DC voltage to ensure proper installation of all battery wiring. Open circuit DC voltage
should measure between 34 volts and 38.5 volts.
7.
Verify that the red and black Anderson connector pair is properly attached to the left side of the
CPR
TM
module.
3.2 battery Installation and Connection,
continued
3.2.2
36V Battery Installation Procedure
+
-
+
-
+
-
CABINET FRONT
RED
BLACK
Fuse
Red and Black
Anderson
Connector
Fig. 3-6, 36V Battery Connections – single string P/N 874-202-20