24
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
P108
Motor Overload
100 30
{%} 100
P109
Motor Overload
Type
0
0 Speed Compensation
Ir
100%
60%
30 f
1
0
V0108
1 No Speed Compensation
P110
Start Method
0
0 Normal
1 Start on Power-up
Drive will automatically start when
power is applied.
2 Start with DC Brake
When start command is applied, drive
will apply DC braking according to
P174, P175 prior to starting the motor
3 Auto Restart
Drive will automatically restart after
faults, or when power is applied.
4 Auto Restart with DC Brake
Combines settings 2 and 3
5 Flying Start/Restart #1
• Drive will automatically restart after
faults, or when power is applied.
• After 3 failed attempts, drive will
Auto Restart with DC brake.
• P110 = 5: Performs speed search,
starting at Max Frequency (P103)
• P110 = 6: Performs speed search,
starting at the last output frequency
prior to faulting or power loss
• If P111 = 0, a flying START is
performed when a start command
is applied.
6 Flying Start/Restart #2
motor current rating
P108 = SM2 output rating x 100
Example:
motor = 3 amps; SM2 = 4
amps; P108 = 75%
Note
Do not set above the rated motor current as listed on the motor
dataplate. The motor thermal overload function of the SM2 is UL
approved as a motor protection device. If line power is cycled, the
motor thermal state is reset to cold state. Cycling power after an
overload fault could result in significantly reducing the motor life.