27
Battery Mode
≥92%
ECO Mode
≥98%
BATTERY
DC Voltage
192V/240VDC
Inbuilt Battery of Standard
Model
16*7AH
16*9AH
NO
Charge
Current
Standard Model
1A
Long Time Model
7A
Typical Recharge Time
8 hours recover to 90% capacity
ALARM
Utility Failure
Beep/4s
Battery Low
Beep/1s
Overload
Beep Twice/1s
UPS Fault
Long Beep
ENVIRONMENT
Humidity
20~90% RH @ 0~40
℃
(non-condensing)
Noise Level
≤58dB (1m)
≤60dB (1m)
MANAGEMENT
Standard RS-232 and USB
Supports Windows 98/2000/2003/XP/Vista/2008/7/8
Optional SNMP
Power management from SNMP manager and web browser
PHYSICAL
Dimension(mm) W*D*H
262×580×455(H),
262×580×732(S)
262×580×628(H)
Packing Dimension(mm)
W*D*H
355×682×615(H),
359×687×822(S)
359×687×717(H)
Net Weight(kg)
25.0(H),
73.0(S)
25.5(H),
74.0(S)
38.5(H)
39.0(H)
Gross Weight(kg)
28.5(H),
82.5(S)
29.0(H),
83.5(S)
47.0(H)
47.5(H)
Derate capacity to 70% in CUCF mode and to 90% when the output voltage is adjusted to 208Vac.
3/1 means three phase input and single phase output mode, 1/1 means single phase input and single
phase output mode.
Summary of Contents for 3106