Battery Information 

 

Runtime Chart 

Battery Option 

100% Load 

75% Load 

50% Load 

25% Load 

2kVA 

11 minute Internal, (4) BAT-0373 

11m 

18m 

32m 

1h17m 

32 minute Internal, (4) BBAT-0065 

32m 

47m 

1h17m 

2h44m 

84 minute Internal, (4) BBAT-10032 

1h24m 

1h56m 

3h06m 

7h07m 

186 minute Internal, (8) BBAT-10032 3h06m  4h22m 7h07m 15h39m 

3kVA 

18 minute Internal, (4) BBAT-0065 

18m 

27m 

47m 

1h44m 

50 minute Internal, (4) BBAT-10032 

50m 

1h12m 

1h56m 

4h22m 

116 minute Internal, (8) BBAT-10032 1h56m  2h41m 4h22m 10h09m 

4kVA 

11 minute Internal, (4) BBAT-0065 

11m 

18m 

32m 

1h17m 

34 minute Internal, (4) BBAT-10032 

34m 

50m 

1h23m 

3h06m 

85 minute Internal, (8) BBAT-10032 

1h25m 

1h56m 

3h06m 

7h07m 

 
 