23
WORKSHOP SPECIFICATIONS
XL³ 160
The chassis can be removed from
the enclosure so that the wiring can
be carried out in the workshop if the
enclosure is already installed on site.
The DPX³ 160 can be integrated in cabinets with an adaptor for mounting on a rail
(see section 6).
A height spacer Cat. No. 4 052 26 can be mounted on the same rail so that modular
devices or a modular distribution block can be installed next to the DPX³.
Vistops with side handle are supplied with the accessories needed to locate the
handle on the outside of the cabinet. A template is provided with the side handle for
drilling the side panel.
With the faceplates removed, the chassis can
be removed from the cabinet after unscrewing
the 4 retaining screws (one at each end of the
chassis)
It is very easy to work on the chassis once it
has been removed from the cabinet
The DPX³ 160 is mounted in a low position on a rail: remove the insulating
supports and refit the rail directly on the functional uprights with the two M6x10
screws provided.
The handle is mounted directly on the cabinet
side panel.
Photo with rail in a low position equipped with a DPX³ 160 and a
height spacer Cat. No. 4 052 26
2
WIRING ON CHASSIS ONLY
1
MOUNTING THE DPX³ 160
2
MOUNTING VISTOP 63 TO 160 A
MOUNTING DEVICES