Protection unit
4. Circuit breaker switched OFF:
protection unit display data are shown like below:
N: 0 A
L1: 0 A
L2: 0 A
L3: 0 A
From this page is possible to reach the main page pushing one time the OK button .
7. Setting of current visualization
Every current on circuit breaker can be shown in two different ways: with an histogram or with a
numeric value (both of them calculated with the same accuracy) .
Maximum number of digits, for numeric value, is 4, so for values under 9999, current is expressed in
Amperes, while for values between 10000 and 99999, currents are expressed in kiloAmperes, with
the approximation to nearest lower decimal value:
• Example 1: 1450 Amperes
→
in this case display will show “1450 A”
• Example 2: 12541 Amperes
→
in this case display will show “12 .5 kA”
Histogram can show values between 0 and 1 .2 x I
threshold
, where I
threshold
is threshold current for thermal
protection (Ir) . Each histogram has up to 48 graphical points, each one corresponding to 2% of total
amount, with approximation to nearest lower decimal value:
• Example: I
r
= 1000A
➔
each graphical point corresponds to 20A . If, in this case, I
1
= 18A and
I
2
= 565A, on histogram it will be no graphical points for I
1
and 28 graphical points for I
2
.
Summary of Contents for 0 281 64
Page 1: ...Unité de Protection Juin 17 LE08438AB Réf 0 281 64 65 66 67 68 ...
Page 2: ......
Page 27: ...Protection unit June 17 LE08438AB References 0 281 64 65 66 67 68 ...
Page 28: ......
Page 53: ...53 Protection unit ...
Page 54: ...54 Protection unit ...
Page 55: ...55 Protection unit ...
Page 56: ...LE08438AB ...