SOMMAIRE

Technical data sheet: F01163EN/01  

Updated: 30/03/2015  

             Created: 07/07/2010

Catalogue number(s): 0 882 30

Configuration tool with screen

IR only: The sensor needs IR technology in order to switch on the load.
US only: The sensor needs US technology in order to switch on the 

load.

F

 Alert

A "BEEP" is transmitted before the end of the time delay programmed.

G

 Standby level

Warns of switch-off by lowering the light level before switch-off.

H

 Standby time

Used to adjust the switch-off warning duration.
NB: Choosing an unlimited duration allows there to be a minimum light 

level when no presence is detected.

 

3.2.3 Advanced mode

3. NAVIGATION (CONTINUED)

3. NAVIGATION (CONTINUED)

Standby level

10%

Max: 100%

G

Standby time

No standby

Max: unlimited

H

A

 Calibration

In order to calibrate the sensor, the surrounding light level must first 

be measured using a luxmeter. The measured surrounding light level 

should then be transmitted to the sensor.

Steps for setting the electric light factor:

- Put the light on and close the shutters 

- Wait 2 minutes

-  Measure the light level below the cell using a luxmeter

Enter this value in the tool and send it to the cell. This calibration will be 

acknowledged during the next detection cycle.

Light regulation

Light regulation

B

Sensor parameter

Advanced mode

Files

Sensor PnL

Advanced mode

2

Calibration

Light regulation

Provision of light

Loop type

A

D

C

B

Max. lux: 99,995

Calibration

0000 lux

A

Max. lux: 1275

Provision of light

Auto

C

Closed loop

Open loop

Loop type

Closed loop

D

A

 Time delay

Length of time the load is on after detection. See technical data sheet 
for the associated sensor.

B

 Sensitivity

 

Sets the sensor range (see technical data sheet for the associated 

sensor).

C

 Daylight setpoint

Value at which the load switches on if the light level is less than the 

setting and goes off if it is above this setpoint. The daylight setpoint 

can be set up to a maximum of 1275 lux.

D

 Mode

There are 4 different operating modes.
Auto on/Auto off mode: 

Comes on automatically: 

-  On detection of a presence if there is insufficient natural light.

Turns off automatically: 

- If no presence is detected and at the end of the time delay set. 

-  Or if there is sufficient natural light (regulation function activated).

Any new detection triggers an automatic switch-on if there is 

insufficient light.
Walk-through:

-  If no presence is detected in the 3 minutes following an initial 

detection, the sensor will cut off the load after 3 minutes.

-  If another movement is detected in the 3 minutes following initial 

detection, the device will cut off the load at the end of the set time 

delay.

Manual on/Auto off mode: 

The lighting is switched on manually and switched off automatically: 

-  If no movement is detected at the end of the set time delay.

After switch-off, if another movement is detected within a 30-second 

period, the lighting switches on automatically.

After 30 seconds, the lighting has to be switched on manually.
Partial on/Group off mode:

This mode is used to ungroup circuits that are switched on upon 

detection and circuits that will be switched off at the end of detection.
Example: Upon detection I switch on the main lighting and I can 

control backup lighting manually in parallel. At the end of detection, 

the sensor controls switching off the main lighting and the backup 

lighting circuits.

E

 Detection scheme

This menu concerns the detection technologies. There are several 

possible types of combination.
IR and US: The sensor needs both technologies in order to switch on 

the load.
IR or US: The sensor needs one of these technologies in order to switch 

on the load.
HF only: The sensor needs HF technology in order to switch on the load.

Summary of Contents for 0 882 30

Page 1: ...he product to be measured At a maximum angle of 15 in the axis of the IR transmission and reception LED see figure 4 m 4 m 15 15 Backlit screen automatic switch off Weight 71 g Impact resistance IK04 Operating temperature 5 C to 45 C Storage temperature 20 C to 70 C Recharging Use a mini USB cable not supplied to recharge the configuration tool via a standard USB socket Note Updating software is a...

Page 2: ... 2 3 s 1 2 3 5 4 6 Sensor parameter Advanced mode Files Sensor PnL Sensor parameters 1 1 2 3 Time delay 000 H 15 Min 00 Sec Max time delay 255 H 59 Min 59 Sec A Daylight setpoint 0500 lux Max 1275 lux C Sensitivity Very high US High HF High PIR Very high High Medium Low B Detection scheme E IR and US Maintain IR or US Retrigger IR or US Initial IR and US IR or US HF only PIR and HF PIR or HF IR on...

Page 3: ...oint Value at which the load switches on if the light level is less than the setting and goes off if it is above this setpoint The daylight setpoint can be set up to a maximum of 1275 lux D Mode There are 4 different operating modes Auto on Auto off mode Comes on automatically On detection of a presence if there is insufficient natural light Turns off automatically If no presence is detected and a...

Page 4: ...ode Files Sensor PnL Files 3 Files File name 3 NAVIGATION CONTINUED 3 NAVIGATION CONTINUED The Files menu can be used to display the customised settings saved Up to 26 files can be saved xx H xx MIN xx Sec PIR High US Low Closed loop xxx Lux x Lux Light regulation Mode Detection scheme Detection scheme Detection scheme Alert Time delay Sensitivity Sensitivity Loop type Daylight setpoint Provision ...

Page 5: ...uct documentation is displayed 5 Install the updating file 6 Click on Yes 8 Select the desired language then click OK 7 Click on Yes 9 Click on Next 3 Click on the icon to access software downloading 4 Download the file 3 2 7 Settings 4 1 Installing the software Files Sensor PnL Test Tool config Settings 6 Languages Version Battery A C B Version Firmware X X XX B Languages Français English Italian...

Page 6: ...lete 16 Click on Finish 1 Launch the application shortcut on the Desktop 15 Select Install this driver software anyway 11 Click on Browse to indicate the destination directory 12 Click on Next 13 To create a software icon on your desktop check the corresponding box then click on Next This window summarises the tasks selected earlier 14 Click on Install to confirm these actions or else on Previous ...

Page 7: ...st be switched off Note All technical information is available on Commercial premises office buildings Passage areas and corridors 100 lux Stairs 150 lux Canteens 200 lux First aid room 500 lux Warehouse 100 lux Offices 300 500 lux Conference rooms 500 lux Reception rooms 300 lux Technical drawing 750 lux Manufacturing areas Packaging rooms 300 lux Visual work during manufacturing 1000 lux Assembl...

Page 8: ...lowing products Hexane En 60669 1 Methylated spirit Soapy water Diluted ammonia Bleach diluted to 10 Window cleaning products WARNING Always test before using other special cleaning products Directive CE Product standard EN 60 669 2 1 Environmental standards European Directive 2002 96 EC WEEE Waste Electrical and Electronic Equipment European Directive 2002 95 EC RoHS Restriction of Hazardous Subs...

Reviews: