LCD Panel Index
Abbreviation
Display Content
Meaning
ENA
Enable
DIS
Disable
ESC
Escape
ON
ON
OK
OK
EP
EPO (Emergency Power Off)
AO
Active Open
AC
Active Close
ST 1/2/3
/
/
Input waveform sensitivity 1/2/3
AUT / AON
/
Automatic / Always on
TP
Temperature
CH
Charger
BF
Battery Fault
BR
Battery Replacement
EE
EEPROM Error
Operating Mode Descriptions
Operating Mode Description
LCD Panel
ECO (Efficiency
Corrective
Optimizer) Mode
When the input voltage is within the voltage
regulated range, the UPS powers the output directly
from the mains. When the battery is fully charged in
this mode, the fan stops working to save energy.
Buck Mode
(When AC is
normal)
When the input voltage is higher than the voltage
regulation range, but lower than the high loss point,
the buck AVR (automatic voltage regulation) is
activated.