23
01: Output Voltage Setting
Interface
Setting
For 110/115/120/127 Vac models, you may choose the following output
voltage:
110
: The output voltage is 110Vac
115
: The output voltage is 115Vac
120
: The output voltage is 120Vac (Default)
127
: The output voltage is 127Vac
02: Programmable Outlets (Enable/Disable)
Interface
Setting
Enable or disable programmable outlets.
ENA
: The programmable outlet is enabled
DIS
: The programmable outlet is disabled (Default)
03: Programmable Outlets Setting
Interface
Setting
Set up backup time limits for all programmable outlets.
0-999:
Set the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices in battery
mode. (Default: 999)
04: Site Fault Detection (Enable/Disable)
Interface
Setting
Enable or disable site fault detection.
ENA
: Site fault detection enabled (Default)
DIS
: Site fault detection disabled
05: Autonomy Limitation Setting
Interface
Setting
Sets up backup time for general outlets when in battery mode.
0-999
: setting the backup time in minutes from 0-999 for general outlets
on battery mode.
DIS
: Disable the autonomy limitation and the backup time will depend on
battery capacity. (Default)
NOTE
:
•
When enabled, if the set time duration is less than the programmable
outlet setting, it overrides the latter.
•
When setting as “0”, the backup time will be only 10 seconds.