Janu
ary 201
9
Legrand PDU User Guide 143
Fields
Description
Location (X, Y
and Z)
Describe the sensor's or actuator's location in the data center by typing
alphanumeric values for the X, Y and Z coordinates. See
Sensor/Actuator
Location Example
(on page 145).
If the term "Rack Units" appears in parentheses in the Z location, you must type
an integer number. The Z coordinate's format is determined on the page of
PDU
(on page 102).
Alarmed to
Normal Delay
This field is available for the DX-PIR presence detector only.
It determines the wait time before the Legrand PDU announces that the
presence detector is back to normal after it already returns to normal.
Adjust the value in seconds.
Binary Sensor
Subtype
This field is available for any Raritan contact closure sensor except for
DX2-DH2C2's contact closure sensors.
Determine the sensor type of your contact closure detector.
Contact Closure
detects the door lock or door open/closed status.
Smoke Detection
detects the appearance of smoke.
Water Detection
detects the appearance of water on the floor.
Vibration
detects the vibration of the floor.
Sensor Polarity
This field is available for DX2-CC2 contact closure sensors only.
Determine the normal state of your DX2-CC2.
Normal Open:
The open status of the connected detector/switch is
considered normal. An alarm is triggered when the detector/switch turns
closed.
Normal Closed:
The closed status of the connected detector/switch is
considered normal. An alarm is triggered when the detector/switch turns
opened.