Legrand PDU User Guide 247
Field
Data entered
IP address/hostname
192.168.84.95
To make the Legrand PDU declare the accessibility of the monitored PDU every 15 seconds (3 pings
* 5 seconds) when that PDU is accessible, enter the following data.
Field
Data entered
Number of successful pings to enable feature 3
Wait time after successful ping
5
To make the Legrand PDU declare the inaccessibility of the monitored PDU when that PDU becomes
inaccessible for around 12 seconds (4 seconds * 3 pings), enter the following data.
Field
Data entered
Wait time after unsuccessful ping
4
Number of consecutive unsuccessful pings for
failure
3
To make the Legrand PDU stop pinging the target PDU for 60 seconds (1 minute) after the PDU
inaccessibility is declared, enter the following data. After 60 seconds, the Legrand PDU will re-ping
the target PDU,
Field
Data entered
Wait time before resuming pinging after failure 60
The "Number of consecutive failures before disabling feature (0 = unlimited)" can be set to any value
you want.
5. Click
Create.
Step 2: Create an event rule to send SNMP notifications for the target PDU
1. Choose Device Settings > Event Rules.
2. Click
.
3. Select the Enabled checkbox to enable this new rule.
4. Configure the following.
Field/setting
Data specified
Rule name
Send SNMP notifications for PDU
(192.168.84.95) inaccessibility
Event
Choose Server Monitoring > 192.168.84.95
> Unreachable
Trigger condition
Select the Unreachable radio button
This will make the Legrand PDU react only when the target PDU becomes inaccessible.
5. Select the System SNMP Notification Action.
Note: If you have not configured the System SNMP Notification Action to specify the SNMP destination(s),
see
Editing or Deleting a Rule/Action
(on page 231).