270 Legrand PDU User Guide
Hardware Issue Detection
This page lists any internal hardware issues Legrand PDU has detected, including current events and
historical records.
Choose Maintenance > Hardware Failures, and the page similar to either of the following diagrams opens.
NO hardware failures detected:
Hardware failure(s) detected:
Hardware Failure alerts on the Dashboard page:
Note that
current
hardware failure events, if any, will also display on the
Dashboard
(on page 95).
Hardware failure types:
Hardware issues
Description
Network device not
detected
A specific networking interface of Legrand PDU is NOT detected.
I2C Bus stuck
A specific I2C bus is stuck, which affects the communication with
sensors.
Slave controller not
reachable
Communication with a specific slave controller fails.
Slave controller
malfunction
A specific slave controller does not work properly.
Outlet power state
inconsistent
The physical power state of a specific outlet is different from the
chosen power state set by the software.