308 Legrand PDU User Guide
Sensor type
Description
activeEnergy
Active energy sensor
unbalancedCurrent
Unbalanced load sensor
lineFrequency
Line frequency sensor
Displayed information:
Without the parameter "details," only the reading, state, threshold, deassertion hysteresis and assertion
timeout settings of the specified inlet sensor are displayed.
With the parameter "details," more sensor information is displayed, including resolution and range.
If the requested sensor type is not supported, the "Sensor is not available" message is displayed.
Additional sensors supported by Legrand PDUs:
The CLI command(s) listed above can be also applied to the following sensors. Note that the measurement
unit of current values in CLI is
A
, not mA.
Sensor type
Description
peakCurrent Peak
current
sensor
reactivePower
Reactive power sensor
displacementPowerFa
ctor
Displacement power factor sensor
phaseAngle
Inlet phase angle sensor
Inlet Pole Sensor Threshold Information
This command syntax shows the specified inlet pole sensor's threshold-related information.
#
show sensor inletpole <n> <p> <sensor type>
To show detailed information, add the parameter "details" to the end of the command.
#
show sensor inletpole <n> <p> <sensor type>
details
Variables:
<n> is the number of the inlet whose pole sensors you want to query. For a single-inlet PDU, <n> is
always 1.
<p> is the label of the inlet pole whose sensors you want to query.
Pole
Label
<p>
Current sensor
Voltage sensor
1
L1
L1
L1 - L2
2
L2
L2
L2 - L3
3
L3
L3
L3 - L1