Janu
ary 201
9
320 Legrand PDU User Guide
PDU Configuration Commands
A PDU configuration command begins with
pdu
. You can use the PDU configuration commands to change
the settings that apply to the whole Legrand PDU device.
Changing the PDU Name
This command changes the device name of Legrand PDU.
config:#
pdu name "<name>"
Variables:
<name> is a string comprising up to 64 ASCII printable characters. The <name> variable must be
enclosed in quotes when it contains spaces.
Setting the Outlet Power-On Sequence
This section applies to outlet-switching capable models only.
This command sets the outlet power-on sequence when the PDU powers up.
config:#
pdu outletSequence <option>
Variables:
<option> is one of the options:
default
, or a comma-separated list of outlet numbers.
Option
Description
default
All outlets are switched ON in the ASCENDING
order (from outlet 1 to the final outlet) when the
Legrand PDU powers up.
A comma-
separated list of
outlet numbers
All outlets are switched ON in the order you
specify using the comma-separated list.
The list must include all outlets on the PDU.
Setting the Outlet Power-On Sequence Delay
This section applies to outlet-switching capable models only.
This command sets the delays (in seconds) for outlets when turning on all outlets in sequence.