Janu
ary 201
9
414 Legrand PDU User Guide
Power Cycling the Outlet(s)
This section applies to outlet-switching capable models only.
This command power cycles one or multiple outlets.
#
power outlets <numbers> cycle
To quicken the operation, you can add the parameter "/y" to the end of the command, which confirms the
operation.
#
power outlets <numbers> cycle
/y
Variables:
<numbers> is one of the options:
all
, an outlet number, a list or a range of outlets.
Option
Description
all
Power cycles all outlets.
A specific outlet
number
Power cycles the specified outlet.
A comma-
separated list of
outlets
Power cycles multiple, inconsecutive or
consecutive outlets.
For example, to specify 7 outlets -- 2, 4, 9, 11, 12,
13 and 15, type
outlets 2,4,9,11-13,15
.
A range of
outlets with a
hyphen in
between
Power cycles multiple, consecutive outlets.
For example, to specify 6 consecutive outlets -- 3,
4, 5, 6, 7, 8, type
outlets 3-8
.
If you entered the command without "/y", a message appears, prompting you to confirm the operation. Then:
Type
y
to confirm the operation, OR
Type
n
to abort the operation
Canceling the Power-On Process
This section applies to outlet-switching capable models only.
After issuing the command to power on ALL outlets, you can use the following command to stop the
power-on process.
#
power cancelSequence
To quicken the operation, you can add the parameter "/y" to the end of the command, which confirms the
operation.
#
power cancelSequence /y