Janu
ary 201
9
508 Legrand PDU User Guide
Reserving IP in Windows
To reserve the IP address of any network interface in the Windows DHCP server, you must convert that
interface's client identifier into
hexadecimal
ASCII codes.
For each interface's client identifier, see
Reserving IP Addresses in DHCP Servers
(on page 506).
In the following illustration, it is assumed that the Legrand PDU serial number is PEG1A00003.
Windows IP address reservation illustration:
1. Convert the client identifier of the desired network interface into ASCII codes (
hexadecimal
).
Interface
Client identifier conversion
ETH1
PEG1A00003 = 50 45 47 31 41 30 30 30 30 33
ETH2 PEG1A00003
-ETH2
= 50 45 47 31 41 30 30 30 30 33
2D 45 54 48 32
The suffix comprising the dash symbol and the
word "ETH2" is also converted.
WIRELESS PEG1A00003
-WIRELESS
= 50 45 47 31 41 30 30 30
30 33
2D 57 49 52 45 4C 45 53 53
The suffix comprising the dash symbol and the
word "WIRELESS" is also converted.
BRIDGE
PEG1A00003 = 50 45 47 31 41 30 30 30 30 33
2. In your DHCP server, bring up the New Reservation dialog, and separate the converted ASCII codes
with spaces.
For example, to reserve the ETH1 interface's IP address, enter the following data in the dialog.
Field
Data entered
IP address
The IP address you want to reserve.
MAC address
The following ASCII codes.
50 45 47 31 41 30 30 30 30 33
Other fields
Configure as needed.