310 Legrand PDU User Guide
Displayed information:
Without the parameter "details," only the reading, state, threshold, deassertion hysteresis and assertion
timeout settings of the specified overcurrent protector sensor are displayed.
With the parameter "details," more sensor information is displayed, including resolution and range.
Environmental Sensor Threshold Information
This command syntax shows the specified environmental sensor's threshold-related information.
#
show sensor externalsensor <n>
To show detailed information, add the parameter "details" to the end of the command.
#
show sensor externalsensor <n>
details
External sensor 3 (Temperature):
Reading: 31.8 deg C
State: normal
Active Thresholds: Sensor specific thresholds
Default Thresholds for Temperature sensors:
Lower critical threshold: 10.0 deg C
Lower warning threshold: 15.0 deg C
Upper warning threshold: 30.0 deg C
Upper critical threshold: 35.0 deg C
Deassertion hysteresis: 1.0 deg C
Assertion timeout: 0 samples
Sensor Specific Thresholds:
Lower critical threshold: 8.0 deg C
Lower warning threshold: 13.0 deg C
Upper warning threshold: 28.0 deg C
Upper critical threshold: 33.0 deg C
Deassertion hysteresis: 1.0 deg C
Assertion timeout: 0 samples
Variables:
<n> is the environmental sensor number. The environmental sensor number is the ID number assigned
to the sensor, which can be found on the Peripherals page of the Legrand PDU web interface.
Displayed information:
Without the parameter "details," only the reading, threshold, deassertion hysteresis and assertion
timeout settings of the specified environmental sensor are displayed.
With the parameter "details," more sensor information is displayed, including resolution and range.
Note: For a state sensor, the threshold-related and accuracy-related data is NOT available.