Legrand PDU User Guide 311
Environmental Sensor Default Thresholds
This command syntax shows a certain sensor type's default thresholds, which are the initial thresholds
applying to the specified type of sensor.
#
show defaultThresholds <sensor type>
To show detailed information, add the parameter "details" to the end of the command.
#
show defaultThresholds <sensor type>
details
Variables:
<sensor type> is one of the following numeric sensor types:
Sensor types
Description
absoluteHumidity
Absolute humidity sensors
relativeHumidity Relative humidity sensors
temperature Temperature
sensors
airPressure
Air pressure sensors
airFlow
Air flow sensors
vibration Vibration
sensors
all
All of the above numeric sensors
Tip: You can also type the command without
adding this option "all" to get the same data.
Displayed information:
Without the parameter "details," only the default upper and lower thresholds, deassertion hysteresis and
assertion timeout settings of the specified sensor type are displayed.
With the parameter "details," the threshold range is displayed in addition to default thresholds settings.
Security Settings
This command shows the security settings of the Legrand PDU.
#
show security
To show detailed information, add the parameter "details" to the end of the command.
#
show security
details
Displayed information:
Without the parameter "details," the information including IP access control, role-based access control,
password policy, and HTTPS encryption is displayed.
With the parameter "details," more security information is displayed, such as user blocking time, user idle
timeout and front panel permissions (if supported by your model).