Legrand PDU User Guide 43
Exception: You CANNOT cascade DX-PD2C5 sensor packages. A Legrand PDU supports only one
DX-PD2C5.
3. Connect the first DX sensor package to the Legrand PDU by plugging its cable's connector into the
RJ-45 SENSOR port of the Legrand PDU.
4. If needed, connect a DPX2 sensor package to the end of the DX chain. See
Connecting a DPX2
Sensor Package to DX2, DX or DPX3
(on page 46).
DPX3 Sensor Packages
A DPX3 sensor package features the following:
Its connection interface is RJ-45.
You can cascade a maximum of 12 DPX3 sensor packages.
Numbers
Components
RJ-45 ports, each of which is located on
either end of a DPX3 sensor package.
LED for indicating the sensor status.
To connect DPX3 to the Legrand PDU:
1. Connect a standard network patch cable (CAT5e or higher) to either RJ-45 port on the DPX3 sensor
package.
2. If you want to cascade DPX3 sensor packages, get an additional standard network patch cable (CAT5e
or higher) and then:
a. Plug one end of the cable into the remaining RJ-45 port on the prior DPX3.
b. Plug the other end into either RJ-45 port on an additional DPX3.