Janu
ary 201
9
Legrand PDU User Guide 49
2. The cable has two RJ-12 sensor ports. Connect DPX sensor packages to the cable's sensor ports.
3. Repeat the above steps if there are additional SENSOR ports on your Legrand PDU.
Supported Maximum DPX Sensor Distances
When connecting the following DPX sensor packages to the Legrand PDU, you must follow two restrictions.
DPX-CC2-TR
DPX-T1
DPX-T3H1
DPX-AF1
DPX-T1DP1
Sensor connection restrictions:
Connect a DPX sensor package to the Legrand PDU using the sensor cable pre-installed (or provided)
by Raritan. You MUST NOT extend or modify the sensor cable's length by using any tool other than the
Raritan's sensor hubs.
If using a DPX-ENVHUB4 sensor hub, the cabling distance between the Legrand PDU and the sensor
hub is up to 33' (10 m).
Maximum distance illustration:
The following illustrates the maximum distance when connecting DPX sensor packages with a maximum 16'
(5 m) sensor cable to the Legrand PDU via a sensor hub.
The sum of a DPX-T3H1 sensor cable's length is 16 feet (5 meters).