1 Introduction

This manual contains information for users of the Niky 1000/1500 models.

You are advised to read this handbook carefully before installing your uninterruptible power sup-

ply, meticulously following the instructions given herein.

The UPS NIKY is only been made for civil or industrial use; it is not in conformity with the standards 

for electro-medical equipment.

•  The UPS NIKY has been designed to supply data processing equipment. The load applied must 

not exceed the one indicated on the rear label of your UPS.

•  The ON/OFF button of your UPS does not electrically isolate the internal parts. To isolate your 

UPS unplug it from the mains power socket.

•  Do not open the UPS container since there may be parts inside with dangerously high voltage 

even when the mains plug is disconnected; there are no parts inside that the user can repair.

•  The UPS NIKY has been designed to work in closed, clean rooms where there are no inflammable 

liquids or corrosive substances and where it is not too damp.

•  Do not place near equipments that generate strong electro-magnetic fields and/or near equi-

pments that are sensible to electro-magnetic fields. (engines, floppy disks, speakers, adapters, 

monitors, video, etc...)

•  Do not pour any liquid on the UPS or inside the UPS.
•  Do not place the UPS in humid environment or near liquid, such as water, chemical solution…
•  Do not expose the UPS to the direct sunlight or any heat sorces.
•  Keep the ventilation slits clean to dissipate the heat of the UPS.
•  Use grounded power cable to connect the UPS to the mains supply.
•  Do not plug laser printers into the UPS because of their high start-up current.
•  Do not plug house electric equipments, such as hair dryer,air conditioner, and refrigerator into 

the UPS outlets.

2 Conditions of use

®

Summary of Contents for 310004

Page 1: ...1500 Index 1 Introduction 14 2 Conditions of use 14 3 Installation 15 4 Signals and controls 15 5 Overload and self shutdown 16 6 Features 16 7 Changing batteries 17 8 Possible malfunctioning 18 9 Technical features 19 ...

Page 2: ...s plug is disconnected there are no parts inside that the user can repair The UPS NIKY has been designed to work in closed clean rooms where there are no inflammable liquids or corrosive substances and where it is not too damp Do not place near equipments that generate strong electro magnetic fields and or near equi pments that are sensible to electro magnetic fields engines floppy disks speakers ...

Page 3: ...ase back up time availa ble during black out will be shorter LED indicators The different colours of the LEDs on the front panel indicate the following LED1 Fixed green mains present and regular Green flashing every 2 sec batteries are recharging LED2 Fixed yellow no mains running on battery LED3 Fixed red overload alarm LED4 Red flashing every 0 5 sec autonomy in reserve Acoustic signals Intermit...

Page 4: ... self text is executed each time the UPS is switched on to provide a reliable operation Battery Protection Automatic battery test and deep discharge protection DC start capability The UPS can be switched on in DC mode battery operation rete provided the load does not exceed 80 of the UPS rated power UPS power supplied outlets This is a line interactive UPS equipped with AVR that allows to feed the...

Page 5: ...ones etc against overvoltage 6 Features Caution Opening repairing or replacing parts inside the UPS must always be carried out by specialized technical personnel only First of all switch off the UPS with the ON OFF button located on the front panel then unplug the power cable from the 230V outlet socket 1 Switch off the uninterruptible power supply 2 Unplug the power cable from the mains socket 3 ...

Page 6: ... shuts down or immediately signals it is close to the operating limit The UPS has operated with no mains voltage for a long time and has not been able to recharge the battery Recharge it for at least 6 hours by connecting the uninterruptible power supply to the mains The battery is flat due to not using the UPS for a long period Recharge it for at least 6 hours by connecting the uninterruptible po...

Page 7: ...n condensing Degree of protection as per IEC529 IP20 Noise level at 1 meter 40 dBA Electrical input specifications Rated input voltage 230 V Range of input voltage 175 285VAC Rated input frequency 50 60 Hz 5Hz Maximum input current 6 2 Arms 8 5 Arms Number of input phases Single phase Waveform on output With battery operation step wave Type of operation line interactive Electrical specifications o...

Page 8: ...ve output capacity on non linear load 600 W 900 W Apparent output capacity on non linear load 1100 VA 1500 VA Battery operation Operating time to 80 of the load 5 min 5 min Charging time 10 12 h at the end of operating range Technical data and number of batteries n 2 maintenancefree sealed leadacid batteries 12V 7 2 Ah n 2 maintenance free sealed lead acid battery 12V 9 Ah Standards Electromagneti...

Page 9: ...atus Leds 2 Power Switch 3 Telephone fax modem or network protection 4 Output sockets 5 AC Input with AC Fuse 6 USB Serial Interface 7 RS232 Serial Interface 3 100 13 3 100 14 1 1 2 7 6 3 5 5 7 6 3 3 100 04 3 100 05 4 4 5 7 6 3 4 3 100 26 3 100 27 ...