1 / 26
87045 LIMOGES Cedex
Telephone number: +33 (0)5 55 06 87 87
–
Fax: +33 (0)5 55 06 88 88
DX³ 4
-pole RCBO
6000 A/10 kA
Cat.
N°(
s) : 4 111 85, 86, 87, 88, 89 / 4 112 04, 05, 06, 07,
4 112 08, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33, 34, 35,
4 112 36, 37, 38, 39, 40, 41, 42, 44, 45, 46, 47, 49, 50, 51,
4 112 52 / 4 113 50, 56, 57, 59, 60, 61, 62, 80, 81
CONTENTS PAGE
1. Description, use .................................. 1
2. Range ................................................. 1
3. Overall dimensions .............................. 1
4. Preparation - Connection ..................... 1
5. General characteristics ........................ 3
6. Compliance and approvals ................ 15
7. Curves .............................................. 16
8. Auxiliaries and accessories ............... 25
9. Safety ................................................ 25
1. DESCRIPTION - USE
Residual Current Operated Circuit Breaker (RCBO) with positive
contact indication for control, protection against short circuits and
overload and isolation of electrical circuits, protecting people from
direct and indirect contact and protecting installations from
insulation faults.
Symbol:
Technology:
. Limiting device
. Simultaneous control of all poles for closing and opening (trip-free
mechanism)
2. RANGE
Polarity:
- 4 protected poles
Width:
. 4 modules (4 x 17.8 mm = 71,2 mm)
Rated currents In:
10 / 13 / 16 / 20/ 25/ 32 A
Magnetic tripping curve:
. C (between 5 and 10 In)
. B (between 3 and 5 In)
Type:
. AC (sinusoidal differential alternating current)
. A (residual current with a DC component)
. F (immunised against false tripping). F products are also A type.
Sensitivity
–
Operating time:
. 30 mA - instantaneous
. 300 mA - instantaneous
. 1,000 mA - instantaneous
2. RANGE
(continued)
Rated voltage and frequency:
. 230/400 V~, 50 Hz with standard tolerances
. 240/415 V~, 50 Hz with standard tolerances
Maximum operating voltage:
. 440 V~, 50 Hz with standard tolerances
Breaking capacity:
. Icn = 6000 A in accordance with standard EN/IEC 61009-1
. Icu = 10 kA in accordance with standard EN/IEC 60947-2
3. OVERALL DIMENSIONS:
4. PREPARATION - CONNECTION
Mounting:
. On symmetrical EN 60.715 rail or DIN 35 rail
Operating positions:
. Vertical horizontal upside down On the side
Power supply:
. Either from the top or the bottom
Technical data sheet: F01315EN/03
Updated on: 30/05/2018
Created on: 27/05/11