11 / 26
DX³ 4
-pole RCBO
6000 A/10 kA
Cat. N°(s) :
4 111 85, 86, 87, 88, 89 / 4 112 04, 05, 06, 07,
4 112 08, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33, 34, 35,
4 112 36, 37, 38, 39, 40, 41, 42, 44, 45, 46, 47, 49, 50, 51,
4 112 52 / 4 113 50, 56, 57, 59, 60, 61, 62, 80, 81
5. GENERAL CHARACTERISTICS
(continued)
Discrimination with upstream fuses, only for sensitivities 300mA and 1000mA :
. Discrimination limit with a voltage of 230 V ~ (Values in A)
Upstream fuse aM type
Downstream RCBO
25A
32A
40A
50A
63A
80A
100A
125A
160A
DX³ 6000A
B and C curves
10A
-
1100
1700
2500
5000
T
T
T
T
13A
-
1000
1400
2100
4000
T
T
T
T
16A
-
1000
1400
2100
4000
T
T
T
T
20A
-
-
1300
1800
3400
5100
T
T
T
25A
-
-
1100
1600
3000
4500
T
T
T
32A
-
-
-
1300
2400
3800
5000
T
T
Discrimination with upstream MCBs , only for sensitivities 300mA and 1000mA :
. Discrimination limit with a voltage of 230 V ~ (Values in A)
Upstream MCB
DX³ 4500/6 kA
-
DX³ 6000/10 kA
-
DX³ 10000/16 kA
B curve
Downstream RCBO
10A
13A
16A
20A
25A
32A
40A
50A
63A
80A
100A
125A
DX³ 6000A
B and C curves
10A
-
-
-
80
100
128
160
200
252
3000
5000* T*
13A
-
-
-
-
100
128
160
200
252
2500
4000
6000*
16A
-
-
-
-
-
128
160
200
252
2000
3600
5500*
20A
-
-
-
-
-
-
160
200
252
1600
3000
4000
25A
-
-
-
-
-
-
-
200
252
1300
2400
3300
32A
-
-
-
-
-
-
-
-
252
1000
1800
2700
Upstream MCB
DX³ 3000
-
DX³ 4500/6 kA
-
DX³ 6000/10 kA
-
DX³ 10000/16 kA
C curve
Downstream RCBO
10A
13A
16A
20 A
25A
32A
40A
50A
63A
80A
100A
125A
DX³ 6000A
B and C curves
10A
-
98
120
150
187
240
300
375
472
3000
5000* T*
13A
-
-
120
150
187
240
300
375
472
2500
4000* 6000*
16A
-
-
-
150
187
240
300
375
472
2000
3600* 5500*
20A
-
-
-
-
187
240
300
375
472
1600
3000
4000*
25A
-
-
-
-
-
240
300
375
472
1300
2400
3300*
32A
-
-
-
-
-
-
300
375
472
1000
1800
2700
. T = Total discrimination
. *: If the discrimination value stated in the table is greater than the breaking capacity of the upstream circuit breaker then the breaking capacity
of the upstream device must be taken as the discrimination value (the discrimination value may not exceed the breaking capacity of the
upstream device).
Technical data sheet: F01315EN/03
Updated on: 30/05/2018
Created on: 27/05/11