DX³ 4

-pole RCBO  

6000 A/10 kA 

 

Cat. N°(s) : 

4 111 85, 86, 87, 88, 89  / 4 112 04, 05, 06, 07, 

4 112  08, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33, 34, 35, 
4 112 36, 37, 38, 39, 40, 41, 42, 44, 45, 46, 47, 49, 50, 51, 
4 112 52 / 4 113 50, 56, 57, 59, 60, 61, 62, 80, 81 

 

 

5. GENERAL CHARACTERISTICS 

(continued) 

Discrimination with upstream fuses, only for sensitivities 300mA and 1000mA : 

. Discrimination limit with a voltage of 230 V ~ (Values in A) 
 

 

Upstream fuse aM type 

Downstream RCBO 

25A 

32A 

40A 

50A 

63A 

80A 

100A 

125A 

160A 

DX³ 6000A 

 

B and C curves 

10A 

1100 

1700 

2500 

5000 

T

 

T

 

T

 

T

 

13A 

1000 

1400 

2100 

4000 

T

 

T

 

T

 

T

 

16A 

1000 

1400 

2100 

4000 

T

 

T

 

T

 

T

 

20A 

1300 

1800 

3400 

5100 

T

 

T

 

T

 

25A 

1100 

1600 

3000 

4500 

T

 

T

 

T

 

32A 

1300 

2400 

3800 

5000 

T

 

T

 

 

Discrimination with upstream MCBs , only for sensitivities 300mA and 1000mA : 

. Discrimination limit with a voltage of 230 V ~ (Values in A) 

 

 

Upstream MCB 

 

DX³ 4500/6 kA 

DX³ 6000/10 kA 

DX³ 10000/16 kA 

 

B curve 

Downstream RCBO 

10A 

13A 

16A 

20A 

25A 

32A 

40A 

50A 

63A 

80A 

100A 

125A 

DX³ 6000A 

 

B and C curves 

10A 

80 

100 

128 

160 

200 

252 

3000 

5000*  T* 

13A 

100 

128 

160 

200 

252 

2500 

4000 

6000* 

16A 

128 

160 

200 

252 

2000 

3600 

5500* 

20A 

160 

200 

252 

1600 

3000 

4000 

25A 

200 

252 

1300 

2400 

3300 

32A 

252 

1000 

1800 

2700 

 

 

Upstream MCB 

 

DX³ 3000 

DX³ 4500/6 kA 

DX³ 6000/10 kA 

DX³ 10000/16 kA

 

C curve 

Downstream RCBO 

10A 

13A 

16A 

20 A 

25A 

32A 

40A 

50A 

63A 

80A 

100A 

125A 

DX³ 6000A 

 

B and C curves 

10A 

98 

120 

150 

187 

240 

300 

375 

472 

3000 

5000*  T* 

13A 

120 

150 

187 

240 

300 

375 

472 

2500 

4000*  6000* 

16A 

150 

187 

240 

300 

375 

472 

2000 

3600*  5500* 

20A 

187 

240 

300 

375 

472 

1600 

3000 

4000* 

25A 

240 

300 

375 

472 

1300 

2400 

3300* 

32A 

300 

375 

472 

1000 

1800 

2700 

. T = Total discrimination 
 
. *: If the discrimination value stated in the table is greater than the breaking capacity of the upstream circuit breaker then the breaking capacity 
of  the  upstream  device  must  be  taken  as  the  discrimination  value  (the  discrimination  value  may  not  exceed  the  breaking  capacity  of  the 
upstream device). 

 

 

 

Technical data sheet: F01315EN/03 

Updated on: 30/05/2018 

Created on: 27/05/11 

 

 

Summary of Contents for 4 111 85

Page 1: ...es for closing and opening trip free mechanism 2 RANGE Polarity 4 protected poles Width 4 modules 4 x 17 8 mm 71 2 mm Rated currents In 10 13 16 20 25 32 A Magnetic tripping curve C between 5 and 10 I...

Page 2: ...ed Cage terminals with release and captive screws Terminals fitted with shutters preventing a cable being placed under the terminal with the terminal partly open or closed Alignment and spacing of the...

Page 3: ...nd contacts closed Trip indication on residual current fault Yellow indicator on the front Locking Padlocks possible in the open or closed positions with padlock support Cat No 4 063 03 and 5 mm padlo...

Page 4: ...C 61009 1 Tested with 20 000 operations with no load Electrical endurance Compliant with standard EN IEC 61009 1 Tested with 10 000 operations with load at In x Cos 0 9 Tested with 2 000 residual curr...

Page 5: ...ristics of a RCBO are modified depending on the ambient temperature which prevails in the cabinet or enclosure where the RCBO is located Reference temperature 30 C in accordance with standard IEC EN 6...

Page 6: ...ristics of a RCBO are modified depending on the ambient temperature which prevails in the cabinet or enclosure where the RCBO is located Reference temperature 30 C in accordance with standard IEC EN 6...

Page 7: ...40 to 125 A 25 A 32 A 40 to 80 A 25 A 32 A 40 to 63 DX 6000 A B and C curves 20 A 16 kA 16 kA 16 kA 25 kA 25 kA 25 kA 36 kA 36 kA 36 kA 50 kA 50 kA 50 kA 25 A 16 kA 16 kA 25 kA 25 kA 36 kA 36 kA 50 k...

Page 8: ...50 to 630 A 500 to 1 250 A 630 to 1600 A DX 6000 A B and C curves 20 A 25 kA 25 kA 25 kA 25 kA 25 KA 25 A 25 kA 25 kA 20 kA 20 kA 32 A 25 kA 25 kA 15 kA 15 kA Upstream MCCB Downstream RCBO DPX 250 ER...

Page 9: ...5 A 32A 40 to 80 A 25 A 32 A 40 to 63 A DX 6000 A B and C curves 20 A 32 kA 32 kA 25 kA 50 kA 50 kA 25 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 25 A 32 kA 25 kA 50 kA 25 kA 50 kA 50 kA 50 KA 50 kA 32 A...

Page 10: ...am MCCB Downstream RCBO DPX 250 ER AB DPX 400 AB DX 6000A B and C curves 32 A 50 kA 50 kA Selectivity between two levels of protection The downstream MCB must always have a magnetic threshold and a ra...

Page 11: ...eam RCBO 10A 13A 16A 20A 25A 32A 40A 50A 63A 80A 100A 125A DX 6000A B and C curves 10A 80 100 128 160 200 252 3000 5000 T 13A 100 128 160 200 252 2500 4000 6000 16A 128 160 200 252 2000 3600 5500 20A...

Page 12: ...300 384 480 600 756 1600 3000 4000 25A 384 480 600 756 1300 2400 3300 32A 480 600 756 1100 1450 2700 Upstream MCB DX 25 kA B curve Downstream RCBO 10A 16A 20A 25A 32A 40A 50A 63A 80 A 100A 12 A DX 600...

Page 13: ...25A 32A 40A 50A 63A 80A DX 6000A B and C curves 10A 120 150 210 500 700 1000 1800 3000 13A 120 150 200 400 600 1200 1500 2500 16A 150 187 300 500 700 1300 2000 20A 187 300 400 500 1000 1600 25A 240 40...

Page 14: ...0 16 kA to 50 kA Downstream RCBO 16A 25A 40A 63A 80A 100A 125A 160A DX 6000A B and C curves 10A 5 T T T T T T T 13A T T T T T T T 16A T T T T T T T 20A 5 5 5 5 6 T T 25A 4 5 4 5 4 5 4 5 T T 32A 3 4 4...

Page 15: ...Discrimination limit with a voltage of 230 V Values in A Upstream MCCB DPX 250 DPX H 250 Electronic DPX DPX H 630 1250 1600 DMX 2500 4000 Downstream RCBO 40A 100A 160A 250A 160 to 4000A DX 6000A B an...

Page 16: ...mpliance with European Union Directives Compliance with Directive 2002 95 EC of 27 01 03 known as RoHS which provides for a restriction on the use of dangerous substances such as lead mercury cadmium...

Page 17: ...12 36 37 38 39 40 41 42 44 45 46 47 49 50 51 4 112 52 4 113 50 56 57 59 60 61 62 80 81 7 CURVES Thermal magnetic tripping curve range typical of B and C curve RCBOs 1 h 0 01 s x In t 1 13 1 45 Thermal...

Page 18: ...24 25 26 27 28 29 30 31 32 33 34 35 4 112 36 37 38 39 40 41 42 44 45 46 47 49 50 51 4 112 52 4 113 50 56 57 59 60 61 62 80 81 7 CURVES continued Average thermal magnetic tripping curves range typical...

Page 19: ...25 26 27 28 29 30 31 32 33 34 35 4 112 36 37 38 39 40 41 42 44 45 46 47 49 50 51 4 112 52 4 113 50 56 57 59 60 61 62 80 81 7 CURVES continued Average thermal magnetic tripping curves range typical of...

Page 20: ...1 4 112 52 4 113 50 56 57 59 60 61 62 80 81 7 CURVES continued Current limiting curves Icc Prospective short circuit symmetrical current rms value in kA Ip Maximum peak value kA 1 Short circuit rms cu...

Page 21: ...12 36 37 38 39 40 41 42 44 45 46 47 49 50 51 4 112 52 4 113 50 56 57 59 60 61 62 80 81 7 CURVES continued Thermal stress limiting curves B curve 4 pole RCBO Icc Prospective short circuit symmetrical c...

Page 22: ...12 36 37 38 39 40 41 42 44 45 46 47 49 50 51 4 112 52 4 113 50 56 57 59 60 61 62 80 81 7 CURVES continued Thermal stress limiting curves C curve 4 pole RCBO Icc Prospective short circuit symmetrical c...

Page 23: ...28 29 30 31 32 33 34 35 4 112 36 37 38 39 40 41 42 44 45 46 47 49 50 51 4 112 52 4 113 50 56 57 59 60 61 62 80 81 7 CURVES continued Tripping current curves Tripping time curve depending on the value...

Page 24: ...28 29 30 31 32 33 34 35 4 112 36 37 38 39 40 41 42 44 45 46 47 49 50 51 4 112 52 4 113 50 56 57 59 60 61 62 80 81 7 CURVES continued Tripping current curves Tripping time curve depending on the value...

Page 25: ...28 29 30 31 32 33 34 35 4 112 36 37 38 39 40 41 42 44 45 46 47 49 50 51 4 112 52 4 113 50 56 57 59 60 61 62 80 81 7 CURVES continued Tripping current curves Tripping time curve depending on the value...

Page 26: ...mbinations of auxiliaries and RCBOs The auxiliaries are installed to the left of the RCBOs Maximum number of auxiliaries 3 Maximum number of 1 module signalling auxiliaries 2 Maximum number of control...