13 / 26
DX³ 4
-pole RCBO
6000 A/10 kA
Cat. N°(s) :
4 111 85, 86, 87, 88, 89 / 4 112 04, 05, 06, 07,
4 112 08, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33, 34, 35,
4 112 36, 37, 38, 39, 40, 41, 42, 44, 45, 46, 47, 49, 50, 51,
4 112 52 / 4 113 50, 56, 57, 59, 60, 61, 62, 80, 81
5. GENERAL CHARACTERISTICS
(continued)
Discrimination with upstream MCBs, only for sensitivities 300mA and 1000mA :
. Discrimination limit with a voltage of 230 V ~ (Values in A)
Upstream MCB
DX
³ 25
kA
D curve
Downstream RCBO
10A
16A
20A
25A
32A
40A
50A
63A
80A
10 A
125 A
DX³ 6000A
B and C curves
10A
-
192
240
300
500
700
1000
1800
3000
5000
T
13A
-
-
240
300
400
600
1200
1500
2500
4000
T
16A
-
-
240
300
384
500
700
1300
2000
3600
5500
20A
-
-
-
300
384
480
600
1000
1600
3000
4000
25A
-
-
-
-
384
480
600
800
1300
2400
3300
32A
-
-
-
-
-
480
600
756
1100
1450
2700
Upstream MCB
DX³ 36 kA/DX³ 50 kA
C curve
Downstream RCBO
10A
16A
20A
25A
32A
40A
50A
63A
80A
DX³ 6000
A
B and C curves
10A
-
120
150
210
500
700
1000
1800
3000
13A
-
120
150
200
400
600
1200
1500
2500
16A
-
-
150
187
300
500
700
1300
2000
20A
-
-
-
187
300
400
500
1000
1600
25A
-
-
-
-
240
400
500
800
1300
32A
-
-
-
-
-
300
500
600
1000
Upstream MCB
DX³ 50 kA
B curve
DX³ 50 kA
D curve
Downstream RCBO
≤16A
2 A
25A
32A
40A
50A
63A
10A
16A
20A
25A
32A
40A
50A
63A
DX³ 6000
A
B
and
C
curves
10A -
150
210
500
700
1000 1800 -
192
240
300
500
700
1000 1800
13A -
-
200
400
600
1200 1500 -
-
240
300
400
600
1200 1500
16A -
-
-
300
500
70 1000 -
-
240
300
384
500
700
1300
20A -
-
-
-
400
500
1000 -
-
-
300
384
480
600
1000
25A -
-
-
-
-
500
800
-
-
-
-
384
480
600
800
32A -
-
-
-
-
500
600
-
-
-
-
-
480
600
756
T = Total discrimination
Discrimination is said to be total if there is discrimination up to the value of the breaking capacity (in accordance with EN 60947-2) of the
downstream RCBO.
The downstream RCBO must always have a magnetic threshold and rated current lower than those of the upstream circuit breaker.