3/16
ELIOT Kit STOP&GO Connected
Cat. N°: 4
149 54
4. PREPARATION - CONNECTION
(continued)
List of possible associations:
. DX
3
2P RCCBs
. DX
3
2P RCBOs (2 poles protected or P+N, 1 pole protected)
Association Stop &Go - Protection device:
. To be fitted to the left of 1 module per pole wide DX
3
RCCB’s 2P or
DX
3
RCBO’s ≤ 10000A (1P+N et 2P ≤ 63 A)
. No tool required. Clipped to the associated device by mean of
plastic clamps.
Wiring diagrams:
. Stop&Go
Note: It is not necessary to install a specific protection upstream of
the Stop&Go because it is self-protected
4. PREPARATION - CONNECTION
(continued)
Wiring diagrams
(continued)
:
. Power supply module:
protected by an MCB:
protected by a Fuse holder:
Connection:
. Terminals protected against accidental contact (IP20, wired
devices).
Terminals:
. Stop&Go
Terminal depth: 8 mm.
Stripping length: 8 mm
. Supply module
Terminal depth: 8 mm.
Stripping length: 8 mm
Screw head:
. Stop&Go
Slotted, diameter 3.5 mm
. Supply module
Mixed, slotted and Pozidriv n°1 (UNI7596 type Z1).
Recommended tightening torque:
. Stop&Go
0,4÷0,5 Nm.
. Supply module
1 Nm
Technical data sheet: F02465EN/01
Updated: 28/03/2019
Created: 06/10/2016