ELIOT Kit STOP&GO Connected 

 

Cat. N°: 4

 149 54

 

 

 

4. PREPARATION - CONNECTION

 (continued)

 

Diagnostic procedure

 (continued)

5. Test 1/3 - 

Set the AUTO/MAN selector to “MAN”

 (the Stop&Go 

LED flashes slowly in green) 
Once t

he test is complete, press “Next” to proceed to the next test

                    

 

6. Test 2/3 - 

Set the AUTO/MAN selector to “AUTO” 

(the Stop&Go 

led is steady green) 

Once the test is complete, press “Next” to proceed to the next test.

 

                    

 

7. Test 3/3 - Simulation of a non-permanent fault and a remote 
reclosing 

7.1 

Press the “TEST” button of the protection device associated to 

the Stop&Go (the Stop&Go power handle is down, and the 
isolating handle is up and the Stop&Go led flashes quickly in red) 
7.2 An alert message is displayed 
7.3 

Press on “TURN ON”

 

                    

 

 

 

4. PREPARATION - CONNECTION

 (continued)

 

Diagnostic procedure

 (continued)

7. Test 3/3 - Simulation of a non-permanent fault and a remote 
reclosing

 (continued)

 

7.4 

Press “OK” 

to confirm the reclosing (the two Stop&Go handles 

are upward and the Stop&Go led goes steady green) 

Once the test is complete, press “Finish”.

 

                    

 

 

 

Note: 
a. 

It is always possible to repeat the procedure by pressing “Restart 

test”

 

b. If one or more tests fail: 

- check the connection between the Stop&Go and the Wi-Fi 
interface 
- Repeat the test procedure 

 

 

 

Technical data sheet: F02465EN/01 

Updated: 28/03/2019 

Created: 06/10/2016 

 

 

 

Summary of Contents for 4 149 54

Page 1: ...non permanent fault It reports the information through the Smartphone app Allows the user to remotely switch it ON In case of recurrent non permanent faults the Stop Go will not allow some remote comm...

Page 2: ...e kit to connect at the downstream of the supplier indifferently in one of the two dedicated ports Supply of the Wi Fi Interface Mandatory in 12 VDC via the specific Power supply module and specific s...

Page 3: ...install a specific protection upstream of the Stop Go because it is self protected 4 PREPARATION CONNECTION continued Wiring diagrams continued Power supply module protected by an MCB protected by a...

Page 4: ...lip the Wi Fi module and the power supply on a different DIN row than the Stop Go module 4 PREPARATION CONNECTION continued Diagnostic procedure Once the kit assembly and the electrical connections ha...

Page 5: ...the Stop Go the Stop Go power handle is down and the isolating handle is up and the Stop Go led flashes quickly in red 7 2 An alert message is displayed 7 3 Press on TURN ON 4 PREPARATION CONNECTION...

Page 6: ...site information displayed by the Stop Go continued Device handle status continued Operation sequences continued In case of an Unwanted tripping of the associated device and during the verification o...

Page 7: ...ows to remotely control the Stop Go via the Smartphone app reclosing of the associated device following a fault MAN on site manual control only by the handle of the Stop Go isolating and power handles...

Page 8: ...rogramming mode or to restore factory settings Possible states Pressing time Action t 3 sec Wi Fi interface put in configuration mode via WPS button t 7 sec Wi Fi interface put in configuration mode v...

Page 9: ...ne and laser marking Lateral side marking by laser left side Standard and programming information right side cabling and traceability information Technical data sheet F02465EN 01 Updated 28 03 2019 Cr...

Page 10: ...ype Measurement type Value dBm 802 11b 1Mbps RMS 18 2 802 11g 54Mbps RMS 16 2 802 11n 72 2Mbps RMS 16 2 Characteristics of the fault detection Rd0 non operating rated resistance between the live parts...

Page 11: ...ce against solid and liquid bodies IP 40 IEC EN 60529 Class II front panel with faceplate Resistance to sinusoidal vibrations According to IEC 60068 2 6 Axis x y z Frequency range 5 100 Hz duration 90...

Page 12: ...ream of the associated device to the Stop Go and to protect the power supply module with a fuse holder or an MCB see Wiring diagrams Supply of the ADSL Wi Fi Box The Wi Fi module communicates with an...

Page 13: ...1 2003 corr Feb 2004 A1 2004 A11 2005 A12 2008 Electrical accessories Circuit breakers for overcurrent protection for household and similar installations Part 1 Circuit breakers for a c operation IEC...

Page 14: ...ing switch can be modified to 2 auxiliary contacts 1 module cat n 4 062 66 Electronic EMS CX3 Auxiliary contact Fault signalling module cat n 4 149 29 Control auxiliaries It is forbidden to associate...

Page 15: ...ing command closing of the circuit not allowed Close manually the Stop Go 4 A too recurrent non permanent fault has been detected Remote reclosing command closing of the circuit not allowed Contact yo...

Page 16: ...n MAN mode Remote reclosing command closing of the circuit not allowed Put selector in AUTO position 8 Stop Go in locked position Remote reclosing command closing of the circuit not allowed If it is p...

Reviews: